AC Current transducer APR-B10
Split core transducer for the electronic measurement distorted AC
waveforms current, with galvanic isolation between the primary (High
power) and the secondary circuits (Electronic circuit). Switch selectable
ranges and True RMS 0-5V and 0-10V switch selectable voltage output.
IPN = 10 .. 400 A
Preliminary
Electrical data
Primary Nominal Current
IPN (A.t.RMS)
10,25,50
50,75,100
100,150,200
200,300,400
Analogue Output Signal
VOUT (V)
0-5V or 0-10V
0-5V or 0-10V
0-5V or 0-10V
0-5V or 0-10V
Type
APR 50 B10
APR 100 B10
APR 200 B10
APR 400 B10
R
Load resistance
L
≥ 10
kΩ
VC
Supply voltage
+24 ±5% V DC
Vd
R.m.s. voltage for AC isolation test, 50/60Hz, 1 mn 5
kV
Limitation of voltage output
18
V
Accuracy-Dynamic performance data
X
εL
VOE
ε VOT
TC G
t
r
f
Accuracy @ IPN, TA = 25°C (without offset)
Linearity (0 .. ± IPN)
Electrical offset voltage, TA = 25°C
Thermal drift of VOE
Thermal drift of the gain (% of reading)
Response time @ 90% of I
P
Frequency bandwidth (-3 dB)
< ±1
< ±0.5
< ±0.5
±1
% of IPN
% of IPN
% of IPN
mV/K
±0.1
%/K
< 1000
ms
10 .. 6000 Hz
General data
T
Ambient operating temperature
A
T
Ambient storage temperature
S
m
Mass
-20 .. +60 °C
-20 .. +85 °C
90
g
Protection type
IP20
Reliable isolation according to EN50178, EN61010 300
V AC
Creepage distance
> 5.5
mm
EMC in accordance with EN50082-2
Plastic according to UL94V0, CTI 1
Features
• VFD and SCR waveforms current
measurement
• True RMS output
• Split core type
• 5V & 10V switch selectable voltage
output.
• DIN mounting & Panel mounting
• Eliminates insertion loss
• Switch selectable ranges
Advantages
• Large aperture for cable up to Ø18mm
• High isolation between primary and
secondary circuits
• Easy to mount
Applications
• VFD Controlled Loads:
VFD output indicates how the motor
and attached load are operating.
• SCR Controlled Loads:
Acurate measurement of phase angle
fired or burst fired (time proportioned)
SCRs. Current measurement gives
faster response than temperature
measurement.
• Switching Power Supplies and
Electronic Ballasts:
True RMS sensing is the most
accurate way to measure power
supply or ballast input power.