English
Language : 

AP-B10_1 Datasheet, PDF (1/2 Pages) LEM – AC Current transducer
AC Current transducer AP-B10
Split core transducer for the electronic measurement AC waveforms
current, with galvanic isolation between the primary (High power) and
the secondary circuits (Electronic circuit). Switch selectable ranges
and RMS 0-5V and 0-10V switch selectable voltage output.
IPN = 10 .. 400 A
Electrical data
Primary Nominal Current
Analogue Output Signal
IPN (A.t.RMS)
VOUT (V)
10,25,50
0-5V or 0-10V
50,75,100
0-5V or 0-10V
100,150,200
0-5V or 0-10V
200,300,400
0-5V or 0-10V
RL
Load resistance
V
Supply voltage
C
I
Current Consumption
C
Limitation of voltage output (0-10V)
Limitation of voltage output (0-5V)
Overloaded input current
Type
AP 50 B10
AP 100 B10
AP 200 B10
AP 400 B10
≥ 10
kΩ
+24 ±5% V DC
< 30
mA
14
V
7
V
no limitation
Accuracy-Dynamic performance data
X
εL
VOE
V
εOT
TC G
tr
f
Accuracy @ IPN, TA = 25°C (without offset)
Linearity (0 .. ± IPN)
Electrical offset voltage, TA = 25°C
Thermal drift of V
OE
Thermal drift of the gain (% of reading)
Response time @ 90% of IP
Frequency bandwidth (±1%)
< ±1 % of IPN
< ±0.5 % of IPN
< ±0.5 % of IPN
±1
mV/K
±0.1
%/K
< 150
ms
30 .. 2000 Hz
General data
T
Ambient operating temperature
A
TS
Ambient storage temperature
m
Mass
Protection type
dCp
Creepage distance
dCl
Clearance distance
CTI
Comparative tracking index (Group I)
UL94 classification
-20 .. +60 °C
-20 .. +85 °C
90
g
IP20
5.5
mm
5.5
mm
600
V
V0
Insulation category
V
Rated Voltage
300
V
b
with IEC 61010-1 standards and following conditions :
- Single insulation
- Over voltage category CAT III
- Pollution degree PD2
- None uniform field
V
R.m.s. voltage for AC insulation test, 50Hz, 1mn
5
kV
d
Ve
R.m.s. voltage for partial discharge extinction @ 10pC 1.5
kV
V
w
Peak impulse withstand voltage 1.2/50µs
6.1
kV
If insulated cable is used for the primary circuit, the voltage category
could be improved with the following table :
Cable insulation (primary)
Category
HAR 05
600V CAT III
HAR 07
1000V CAT III
Notes : Installation and maintenance should be done with power supply disconnected.
The operator must have accrediation to install this material.
The users must take care of all protection gurantee against electrical shock.
L. EM Components
Features
• RMS output
• Split core type
• 5V & 10V switch selectable voltage
output
• DIN mounting & Panel mounting
• Eliminates insertion loss
• Switch selectable ranges
Advantages
• Large aperture for cable up to
Ø18mm
• High isolation between primary and
secondary circuits
• Easy to mount
Applications
• Automation systems
Analog current reading for remote
monitoring (e.g. motor) and
software alarms.
• Panelmeters
Simple connection displays power
consumption.
041029/3
www.lem.com