English
Language : 

AK-C420L Datasheet, PDF (1/2 Pages) LEM – AC Current transducer
AC Current transducer AK-C420L
Transducer for the electronic measurement AC sinusoidal waveforms
current, with galvanic isolation between the primary (High power) and
the secondary circuits (Electronic circuit). Jumper selectable ranges
and 4-20mA current output.
IPN = 2 .. 200 A
Electrical data
Primary Nominal Current
I (A.t.RMS)
PN
2, 5
10, 20, 50
100, 150, 200
Analogue Output Signal1) Type
I (mA)
OUT
RoHS
Date Code
4-20
4-20
4-20
AK 5 C420L
AK 50 C420L
AK 200 C420L
MAY 2006
MAY 2006
planned
Vc Supply voltage (Loop powered)
24
R Load resistance
L
see power supply diagram
Vb Rated voltage (CAT III, PD2)
150
Vd RMS Isolation voltage test, 50 Hz, 1mn
3
f
Frequency bandwith
20-100
V DC
V AC
kV AC
Hz
Accuracy - Dynamic performance data
X
Accuracy @ IPN, TA=25°C
tr
Response time @ 90% of IPN
±1
%
< 300
ms
General data
T Ambient operating temperature (0-95% RH)
-20..+50
°C
A
T Ambient storage temperature
S
-20..+85
°C
m Mass
120
g
Safety
IEC 61010-1
EMC
EN 61326
Note: 1) For 4-20mA output model, no saturation output up to 25 mA.
Features
• AC sinusoïdal Measurement
• Average responding
• Current output
• Loop powered transducers
• Panel mounting
• Accurate
• Jumper selectable ranges
Advantages
• Large aperture
• High isolation between primary and
secondary circuits
• Easy to mount
Applications
• Automation systems
Analog current reading for remote
monitoring (e.g. motor).
• Data loggers
Self-powered transducer does not
drain data logger batteries.
• Panel meters
Simple connection displays power
consumption.
Options on request
• DIN mounting
LEM
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
060512/6
Page 1/2
www.lem.com