English
Language : 

PR500 Datasheet, PDF (1/1 Pages) DENSEI-LAMBDA – Rectifier module 500W
PR-SERIES Rectifier module 500W
Ⅵ Model name
PR 500-280
(Low Voltage Directive)
Multigrades : 2 year warranty
Nominal output Nominal output
power
Name of series
voltage
Ⅵ Features
ⅷ marking (Low Voltage Directive)
ⅷ Rectifier module
AC filtering module used in AC front end of DC-DC module.
Connect external filtering capacitor to output.
ⅷ Input 100V/200VAC
ⅷ Output voltage detecting signal (power-on signal)
ⅷ Power failure alarm signal during instant input
ⅷ Wide baseplate temperature: –20 ~ +85°C
Conduction cooling
ⅷ 2 year warranty
Ⅵ Specifications
01. Input voltage range
02. Rated output voltage
03. Max. output current/power
04. Efficiency (typ)
05. Input alarm signal
06. Power on signal
07. Auxiliary power
08. Cooling
09. Operating ambient
temperature
10. Withstand voltage
11. Safety standard
85 ~ 132VAC/170 ~ 265VAC (47 ~ 440Hz) selectable
280VDC (230 ~ 370VDC)
85 ~ 132VAC: 2.1A 500W, 170 ~ 265VAC: 3.15A 750W
95%: 200VAC at full load
Detection signal output when input 10mS or more is interrupted (ACF terminal)
Signal output while output voltage is supplied (ENA terminal)
Connect to control terminal of DC-DC converter module
Auxiliary power output for external signal (AUX terminal: DC16 ~ 20V 10mA max.)
Conduction cooling (Heatsink & airflow has to be chosen according to instruction manual)
Baseplate temperature: –20 ~ +85°C (output derating is different according to condition)
Ambient temperature: above –20°C
Input/output terminal to baseplate: 3.0kVAC for 1 min.
Approved by UL1950 , CSA950(C-UL) and EN60950(BSI)
Ⅵ Product lineup
Model
Input voltage
range
Input current (typ)
Nominal output
voltage
Max. output current
PR500-280
85 ~ 132VAC
170 ~ 265VAC
8.8A (input at 100VAC)
6.6A (input at 200VAC)
280VDC
(230 ~ 370VDC)
2.10A (output at 240VDC)
3.15A (output at 240VDC)
ⅷ Request customer specification for further details of specifications, outline, characteristics, etc.
Read the instruction manual before usage.
ⅷ Contact us about delivery before ordering.
[Input 100VAC]
[Input 200VAC]
Ⅵ Outline drawings
R (in-rush current limiting resistor)
R (in-rush current limiting resistor)
Max. output
power
UL
CSA
EN
500W
750W
⅜⅜⅜
⅜⅜⅜
⅜ : Safety standard approved
Ⅵ Block diagram
For 100/200V input selection, connect
center mode of C1 and C2 to AC(N) of
PR500 connector.
(C1, C2: cap for voltage doubler rectifier
and filtering capacitor)
(Unit: mm)
Note 1: Model name, Input voltage range, Nominal output voltage, Maximum output current
and country of manufacture are shown here.
Note 2: Input & output terminal
110
4-ø2
6-ø0.6