English
Language : 

MC1320 Datasheet, PDF (1/4 Pages) DENSEI-LAMBDA – MC13-SERIES
MC13-SERIES
Ⅵ Features
(1) 2 mounting options :
MC13** Screw mounting type
MC13**DIN Din rail mounting type
(2) Worldwide compliance :
Voltage rating 3 phase AC500V, 10, 20, 30A
(3) Safe design :
Terminal with cover, Low leakage current
(4) Environmental compliance : Lead free soldering
Ⅵ Safety standard
UL1283
CSA Std. C22. 2 No. 8
EN133200
EN133200
Ⅵ Specifications
Model STD type
Items
DIN type
1 Rated Voltage (AC)
2 Rated Current (*1)
3 Test Voltage (terminals to base plate, 1min AC)
4 Isolation Resistance (terminals to base plate, 500VDC)
5 Leakage Current
500V,60Hz
6 DC Resistance (three lines)
7 Temperature Rise
8 Operating Temperature
9 Operating Humidity
10 Storage Temperature
11 Storage Humidity
12 Vibration
13 Weight
MC13**
MC13**DIN
Ⅵ Circuit
MC1306
MC1310
MC1320
MC1330
MC1306DIN
MC1310DIN
MC1320DIN
MC1330DIN
500V (50/60Hz)
6A
10A
20A
30A
2000V (100mA) at 25°C, 70% RH
100MΩ min at 25°C, 70% RH
5.0mA max
90mΩ max
68mΩ max
23mΩ max
11mΩ max
30°C max
-25°C ~ +85°C
30% ~ 95% RH (No Dewdrop)
-40°C ~ +85°C
10% ~ 95% RH (No Dewdrop)
At no operating 10~55~10Hz, Amplitude (Sweep for 1min) 0.825mm constant (Maximum 49.0m/s2)X,Y,Z 1hour each
At no operating 55~250~55Hz, Acceleration (Sweep for 1min) 19.6m/s2, X,Y,Z 1hour each
At no operating 10~55~10Hz, Acceleration (Sweep for 1min) 9.8m/s2, X,Y,Z 1hour each
600g
(Note) : Value for Ta<=50°C For Ta>50°C derate according to the derating curve shown on the right.
Ⅵ Derating
Ⅵ Terminal Explanation
Temperature (°C)
ⅷ Request customer specification for further details of specifications, outline, characteristics, etc.
Read the instruction manual before usage.
ⅷ Contact us about delivery before ordering.
163