English
Language : 

FF-1585-10 Datasheet, PDF (1/1 Pages) JMK Inc. – Operating Voltage = 250/480 V~, 50 / 60 Hz Operating Voltage = 125/208 V~, 50 - 400 Hz
JMK. Inc.
FF-1585-10
Operating Voltage = 250/480 V~, 50 / 60 Hz
Operating Voltage = 125/208 V~, 50 – 400 Hz
Operating Current = 10 A / Phase
Temperature Range = -20 TO 50 Deg. C
Diel. Withstand (L-CASE) = 1500 V~ FOR 1 MIN.
Diel. Withstand (L-L) = 1500 Vdc For 1 Min.
Leakage Current = 3.4 ma @ 250 V~, 60 Hz
Discharge Volt after 1.0 second = 34 V Max.
Maximum Capacitance each line to case =
0.016 µF
Order P/N: FF-1585-10
LINE
BLK
RED
BRN
G/Y
LOAD
BLK
RED
BRN
G/Y
The FF-1585-10 is a delta configuration,
3-phase filter designed for use with large
computers, power distribution units, motor
installations, etc.
The compact size and leads make the filter
package easy to install where size is at a
premium.
USA
EUR
JMK Inc 15 Caldwell Dr. Amherst, NH 03031 PH: 603 886-4100 FX: 603 886-4115
email: info@jmkfilters.com