English
Language : 

CSNR151-004 Datasheet, PDF (3/5 Pages) Honeywell Accelerometers – CSN Series Hall Effect Current Sensors
PERFORMANCE DATA
Definition
Acurrent transducer based on the principle of magnetic compensation. It provides electronic measurement of DC, AC, pulsed
currents and their combinations with galvanic isolation between the primary (high current) and secondary circuits.
Electrical Data
CSNL181 - XXX
CSNM191 - XXX
Nominal current (In)
Measuring range
Measuring Resistance (Rm)
with ±15V
at ±300 A.t max
at ±600 A.t max
Nominal analogue output current
Turns Ratio
Overall accuracy at +25°C
Supply Voltage
Isolation between primary and secondary
: 300 Arms
: 0 to ±600 A
: Rm min Rm max
: 0 ohm 50 ohm at ±500 A.t max
: 0 ohm 10 ohm at ±1000 A.t max
: 150 mA
: 1/2000
: ±0.5% on In
: ±12V to 18V (±5%)
: 7.5 kV rms/50 Hz/1 min
: 500 Arms
: 0 to ±1000 A
: Rm min Rm max
: 0 ohm 50 ohm
: 0 ohm 5 ohm
: 100 mA
: 1/5000
: ±0.5% of In
: ±12V to ±18V (±5%)
: 6.0 kV rms/50 Hz/1 min
Accuracy - Dynamic Performance
Zero offset current at +25°C
Thermal drift of offset current,
between 0°C to +70°C
Linearity
Response time
di/dt accurately followed
Bandwidth
: Max ±0.3 mA
: Typ ±0.3 mA; Max ±0.5 mA
: better than ±0.1%
: better than 500nS
: better than 50 A/µs
: DC to 150 KHz
: Max ±0.2 mA
: Typ ±0.2 mA; Max ±0.3 mA
: better than ±0.1%
: better than 1µs
: better than 50 A/µs
: DC to 100 KHz
General data
Operating temperature
Storage temperature
Current consumption
Secondary internal resistance
Sensor Housing
Signal sense
EMC
: -40°C to +85°C (-40°F to +185°F)
: -40°C to +90°C (-40°F to +194°F)
: Typ 14mA(±18V) + output current
: 25 ohm (at 70°C)
: Insulated plastic case (Bayblend FR1468)
: a positive output current is obtained on
terminal O/Pwhen the primary current
flows in the direction of the arrow
: EN50081-2, EN 50082-2
: -40°C to +85°C (-40°F to +185°F)
: -40°C to +90°C (-40°F to +194°F)
: Typ 14mA(±18V) + output current
: 50 ohm (at 70°C)
: Insulated plastic case (Bayblend FR1468)
: a positive output current is obtained on
terminal O/Pwhen the primary current
flows in the direction of the arrow
: EN50081-2, EN 50082-2
ƽ WARNING
PERSONALINJURY
• DO NOTUSE these products as safety or emergency stop devices, or in any other application
where failure of the product could result in personal injury.
Failure to comply with these instructions could result in death or serious injury.
Electrical Connection
+
+
-
-
ov
Rm
O/P
OUTPUT
Termination
300A:
500A:
Supply Voltage ±12V to ±18V
Supply Voltage ±12V to ±18V
O/PMeasured output signal
Honeywell • Sensing and Control 2