English
Language : 

HID35 Datasheet, PDF (1/2 Pages) HITRON ELECTRONICS CORPORTION – UNIVERSAL AC INPUT AC-DC INDUSTRIAL DIN-RAIL SINGLE OUTPUT 30 WATTS SWITCHING MODE POWER SUPPLIES
H HiTRON
UNIVERSAL AC INPUT AC-DC INDUSTRIAL DIN-RAIL
SINGLE OUTPUT 30 WATTS SWITCHING MODE
POWER SUPPLIES HID35 SERIES
FEATURES:
ACCOMMODATE UNIVERSAL AC SOURCES
MEET UNIVERSAL SAFETY STANDARD AND
INDUSTRIAL UL 508
INDUSTRIAL POWER SUPPLIES FOR
SNAP-ON MOUNTING ON DIN-RAILS
EMI MEET CISPR PUB. 22 & FCC CLASS B
CE MARKING COMPLIANCE
SPECIFICATION
INPUT SPECIFICATION
Input Voltage: Typ. 90-264Vac.
Input Connector: M-T plug connector.
Input Frequency: 47-63Hz.
Inrush Current: ≤30.6A (rms) @230Vac.
Input Current: 0.51A @115Vac, 0.28A @230Vac.
Dielectric Withstand: Meet IEC 60950-1.
EMI: Meet CISPR EN 55022 & FCC B.
No Load Operation: No damage.
Hold-up Time: 18.2mS @115Vac/ 69.6mS @230Vac.
Earth Leakage: Less than 0.41mA @230Vac.
OUTPUT SPECIFICATION
Output Voltage: See Ratings Chart.
Output Current: See Ratings Chart.
Output Wattage: Typ. 30W continuous.
Output Connector: M-T plug connector.
Line Regulation: Typ. 0.1%.
Load Regulation: Vary with output voltage.
Typ. ±0.4%.
Noise & Ripple: Typ. 1% peak to peak.
OVP: Built-in (Latch).
Adjustability: Available at VO1.
LED Indicator: Output indicating.
Overload Protection (OLP):
Fully protected against output overload and short circuit.
Typically set at 115% max. load.
Consult the factory for special OLP setting.
GENERAL SPECIFICATION
Efficiency: Typ. 76%.
Switching Frequency: Fixed freq. 56K Hz.
Circuit Topology: Fixed frequency flyback circuit.
Operating Temperature: -10 to +70°C. Derating from
+60 °C to +70°C by derating 2%/°C.
Storage Temperature: -25 to +85°C.
Temperature Coefficient: Typ. 0.03% /°C.
Transient Response: Peak transient typ. 150mV, recovers in Cooling: Convection cooling for Ta < +60°C.
50.6mS following a 50% load change.
Safety Standard: IEC 60950-1/UL 60950-1 Class I.
Power Density: 1.4 Watt/ Cubic Inch.
Moving air is request for Ta >+ 60°C full load operation.
Construction format: Enclosure metal box with
DIN-clips format.
MTBF Demonstrated: >380,000 hours at full load and
Industrial Grade UL 508.
25°C ambient conditions.
Note: Due to requests in market and advances in technology, specifications subject to change without notification.
-27-
In application