English
Language : 

HDC201P-48B Datasheet, PDF (1/2 Pages) HITRON ELECTRONICS CORPORTION – 36-72VDC INPUT RANGE DC-DC CONVERTER HOT-SWAP CompactPCI QUAD OUTPUT 200 WATTS ACTIVE CURRENT SHARING SWITCHING POWER SUPPLIES
H HiTRON
36-72VDC INPUT RANGE DC-DC CONVERTER HOT-SWAP CompactPCI
QUAD OUTPUT 200 WATTS ACTIVE CURRENT SHARING SWITCHING
POWER SUPPLIES HDC201P-48B SERIES
FEATURES:
200W 3U X 8HP EUROCARD PACKAGE
36-72VDC NOMINAL 48VDC INPUT
INTERNAL OR-ING DIODES FOR
N+1 REDUNDANCY
HOT-SWAPPABLE
THIRD-WIRE CURRENT SHARING
EMI MEET EN 55022 / FCC CLASS B
CE MARKING COMPLIANCE
FULLY COMPLIANT WITH PICMG
SPECIFICATION
INPUT SPECIFICATION
Input Voltage: Typ. 36-72Vdc,nominal input 48Vdc.
Input Connector: Positronic 47-pin PCIH47M400A1.
Inrush Current: Typ. 20A @ nominal input 48Vdc.
Input Current: 5.2A @ nominal input 48Vdc.
Dielectric Withstand: Meet IEC 60950-1 regulation.
EMI: Meet CISPR EN 55022 & FCC Class B.
Remote ON/OFF: Available at [INH#] & [EN#] pins.
Power Fail Signal: Available at [FAL#] pin.
Status LED: <Green> means valid input voltage.
<Amber> means a critical fault.
Thermal Protection (OTP): Installed NTC for thermal
sensor at [DEG#] pin.
OUTPUT SPECIFICATION
Output Voltage: See Ratings Chart.
Output Current: See Ratings Chart.
Output Wattage: Typ. 200W continuous.
Output Connector: Positronic 47-pin PCIH47M400A1.
Line Regulation: Typ. 0.1%.
Load Regulation: Typ. ±1.0-2.0%.
Noise & Ripple: Typ. 1% peak to peak or 50mV,
whichever is greater.
OVP: Built-in at all outputs.
Adjustability: Available at VO1,2&3.
Output Trim: Electrical trim available at VO1/2.[ADJ #]
Hot-Swap: Available.
Remote Sensing: Available at VO1,VO2 & VO3.
Power OK Signal: Available for all outputs.
N+1 Redundancy: Installed with internal OR-ing diodes at
all outputs for N+1 redundancy.
Current Sharing: Third-wire current sharing at VO1,2&3.
Over Current Protection (OCP): Installed in each rail.
Overload Protection (OLP): Fully protected against
output overload or short circuit. Typical 120% max. load.
Consult the factory for special OLP setting.
GENERAL SPECIFICATION
Efficiency: Typ. 79 %.
Operating Temperature: 0 to +50 °C at full load with
Switching Frequency: 110K Hz.
specified air flow. Derates linearly to 50% at +70°C.
Circuit Topology: Forward circuit.
Storage Temperature: -40 to +85 °C.
Transient Response: Typ. 3mS following 25% load-change.
Safety Standard: IEC 60950-1 Class I.
Temperature Coefficient: Typ. ±0.02% / °C.
Construction: Eurocard 3U X 8HP X 160mm
Cooling: At least 20 cfm(600 lfm) moving air is required
CompactPCI format. Front Panel with
to achieve full rating power 200W in a confined area.
either Ordinary handle or Extractor handle. Power Density: 3.7 Watts/ Cubic Inch.
Note: Due to requests in market and advances in technology, specifications subject to change without notification.
-13-
In application