English
Language : 

HAC300S Datasheet, PDF (1/2 Pages) HITRON ELECTRONICS CORPORTION – UNIVERSAL AC INPUT HARMONIC CORRECTION AC-DC HOT-SWAP
H HiTRON
UNIVERSAL AC INPUT HARMONIC CORRECTION AC-DC HOT-SWAP
CompactPCI SERIAL SINGLE OUTPUT WITH STANDBY 312 WATTS
ACTIVE CURRENT SHARING SWITCHING POWER SUPPLIES
HAC300S SERIES
FEATURES:
 312W 3U X 8HP EUROCARD PACKAGE
 WIDE OPERATING TEMPERATURE RANGE
OF -40°C TO +70 °C
 MEET IEC 61000-3-2HARMONIC CORRECTION
 N+1 REDUNDANCY/HOT-SWAPPABLE
 80 Plus GOLD EFFICIENCY
 ACTIVE CURRENT SHARING
 PMBus COMMUNICATION
 FULLY COMPLIANT WITH PICMG
SPECIFICATION
INPUT SPECIFICATION
Input Voltage: Typ. 90-264Vac.
Power Factor Correction: Meet Harmonic Correction
IEC 61000-3-2.Power Factor typ. 0.98-0.99.
Input Connector: FCI 51939-667LF.
Input Frequency: 47-63Hz.
Inrush Current: 5.3Arms at 230Vac.
Input Current: 3A at 115Vac/1.5A at 230Vac.
Dielectric Withstand: Meet IEC 60950-1 regulation.
EMI: Meet EN 55022 / FCC Class B.
Hold-up Time: 18mS at 115 & 230Vac.
Leakage Current: Less than 0.7mA at 230Vac.
Power Fail Signal: Available at [FAL#] pin.
Remote ON/OFF: Available.
Status LED: <Green> means valid input voltage.
<Red> means a critical fault.
<Green> means DC OK.
Thermal Protection (OTP): Installed NTC and
thermostat for thermal sensor at [DEG#] pin.
OUTPUT SPECIFICATION
Output Voltage: See Ratings Chart.
Output Current: See Ratings Chart.
Output Wattage: Typ. 312W continuous.
Output Connector: FCI 51939-667LF.
Line Regulation: Typ. 1%.
Load Regulation: VO1 Typ. ±1%./ Standby Typ. ±5%
Noise & Ripple: Typ. 1% peak to peak.
OVP: Built-in at all outputs.
Adjustability: Available for VO1.
Remote Sensing: Available for VO1.
DC OK: Available for VO1 & +5Vsb.
Hot-Swap: Available.
N+1 Redundancy: Installed with internal OR-ing diodes
at all outputs for N+1 redundancy operation.
Current Sharing: Active current sharing at VO1.
Overload Protection (OLP): Fully protected against output
overload or short circuit. OLP set at 120-130% peak
current at 115Vac. Consult the factory for special
OLP setting.
GENERAL SPECIFICATION
Efficiency: Typ. 90% at 230Vac.
Switching Frequency: 85-100K Hz.
Circuit Topology: LLC circuit.
Transient Response: Peak transient less than 134mV and
recovers within 0.5mS after 25% load-change.
Safety Standard: IEC 60950-1 Class I.
Construction: 3U X 8HP CompactPCI format.
Front Panel with Extractor handle.
Operating Temperature: -40 °C to +70 °C (see note 3),
derate linearly from 100% power at +50 °C to
60% power at +70 °C (Refer to derating curve).
Storage Temperature: -45 to +85 °C.
Cooling: At least 200 LFM moving air is required to achieve
full rating power 312W in a confined area.
Power Density: 5.7 Watts/ Cubic Inch.
NOTE: (1)All measurement are at nominal input, full load and +25°C unless otherwise specifications.
(2)Due to requests in market and advances in technology, specifications subject to change without notification.
(3)A warm-up time 10 minutes is required after cold start at temperature from -40 °C to +0°C.
(4)Tantalum capacitors connected to system is suggested for bettering Ripple & Noise against operating temperature from -40°C to +0°C.
Hitron Electronics Corporation. B4-11, P.O. Box 26-110 Kaohsiung Export Processing Zone Kaohsiung 806 Taiwan
TEL: 886-7-8210410/FAX: 886-7-8419917, 886-7-8210511/E-mail: sales@hitron-e.com/Web-site: www.hitron-e.com
-1-
Edited on March 13, 2013