English
Language : 

70L-ODC Datasheet, PDF (1/2 Pages) Grayhill, Inc – Transient Protection: Meets the requirements of IEEE 472
DC Output Modules
FEATURES
• Transient Protection: Meets the
requirements of IEEE 472, "Surge
Withstanding Capability Test"
• SPST, Normally Open
• UL, CSA, CE, TÜV Certified
• Optical Isolation
• OpenLine® and G5 Modules
Provide Replaceable 5x20mm
Glass Fuses
• Built-in Status LED
• Lifetime Warranty
70L-ODC 70G-ODC
70-ODC
70M-ODC
DIMENSIONS
For complete dimensional drawings, see pages
L-4 or L-5.
FUSES
G5 Fuses are 5 Amp Littelfuse part number
217005 or equivalent. OpenLine® fuses are
3.15 Amp Littelfuse part number 2173.15.
4
STANDARD, G5 PACKAGES
MINIATURE PACKAGE
3
OPENLINE PACKAGE/CH
2
200 VDC STYLE
1
Maximum Current Versus
Ambient Temperature
The chart indicates continuous current to limit
the junction temperatures to 115°C. Information
is based on steady state heat transfer in a 2
cubic foot sealed enclosure.
Fuse kits available, see page L-104.
CIRCUITRY
Standard, Mini, G5
+ LOAD 1
VDC
VOLTAGE
SPIKE
PROTECTION
– LOAD 2
DRIVER
CIRCUIT
Rx
+
3
DC CONTROL
–
4
Fuse and status LED in G5 and OpenLine modules only.
-40˚ -20˚
0
20˚ 40˚ 60˚ 80˚ 100˚
AMBIENT TEMPERATURE (˚C)
Figure 1
OpenLine®
TYPICAL WIRING FOR MODULE 0
GND 5
Vcc 6
A
CH. A
CONTROL 7
CHANNEL A
OPTICAL
ISOLATION
DRIVER
CIRCUIT
B
CH. B
CONTROL
8
MODULE ID 9
2.15K
OPTICAL
ISOLATION
DRIVER
CIRCUIT
CHANNEL B
I/O MODULE
PIN #
+
1
1
LOAD
–
2
2
DC
SUPPLY
+
3
3
DC
SUPPLY
–
4
4
BASE
OR
RACK
LOAD
TERMINAL
BLOCK #
SPECIFICATIONS: By Package Style
Package Style
Specifications
Load Current Range1
Surge Current for 1 Sec.
Maximum Reverse Logic Voltage
Isolation Voltage2
Vibration3
Mechanical Shock4
Storage Temp. Range
Operating Temp. Range
Warranty
Units
A
A
Vdc
Vrms
°C
°C
Std (70-)
0.02-3.5
5
-5
4000
MIL-STD-202
MIL-STD-202
-40 to 125
-40 to 100
Lifetime
Mini (70M-)
0.02-3.0
5
-5
4000
MIL-STD-202
MIL-STD-202
-40 to 125
-40 to 100
Lifetime
1 See Figure 1 for derating.
2 Field to logic and channel-to-channel if Grayhill racks are used.
3 MIL-STD-202, Method 204, 20 G, 10-2000 Hz or IEC68-2-6, 0.15 mm/sec2, 10-150 Hz.
4 MIL-STD-202, Method 213, Condition F, 1500 G or IEC68-2-27, 11 mS, 15g.
G5 (70G-)
0.02-3.5
5
-5
4000
MIL-STD-202
MIL-STD-202
-40 to 125
-40 to 100
Lifetime
OL (70L-)
0.02-2.0/CH
5
-5
2500
IEC68-2-6
IEC68-2-27
-40 to 100
-40 to 85
Lifetime
I/O
8
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com