English
Language : 

GOG96015_17 Datasheet, PDF (1/3 Pages) Green Power Solutions srl – THREE PHASE AC-DC BRIDGE
Green Power Solutions srl
Via Venezia 34D - 10088 Volpiano (TO), Italy
Phone: +39-011-988 2251
Fax: +39-011-988 1358
Web: www.gpsemi.it
e-mail: info@gpsemi.it
GOG9xx15
THREE PHASE AC-DC BRIDGE
Fuse protection
Blown fuse indicators with microswitch
Over temperature switches
Fan loss detection circuit
Snubber for SCR's protections
Extractible stacks for easy field service
LINE VOLTAGE UP TO 690V
DC OUTPUT CURRENT 1500A
Line to line voltage
GOG94015 GOG95015 GOG96015
400 V
500 V
690 V
Characteristic
IDC
DC output current
VINS (rms) Insulation voltage
Conditions
Value
1500 A
3000 V
Value
1500 A
3000 V
Value
1500 A
3000 V
THYRISTOR TRIGGERING CHARACTERISTICS
VGT
Gate trigger voltage
Tj = 25 °C, V D = 5 V
IGT
Gate trigger current
Tj = 25 °C, V D = 5 V
dV/dt
VRRM
Critical rate of rise off-state voltage
Blocking Voltage
Tj= 125 °C
Tj = 125 °C
FUSE TYPE SIBA 2068132.1000 / 2078132.1000
VNF
Rated voltage
INF
Rated current
PVF
Power loss
I²t
Total I2t
At rated current
At 660V
3V
300 mA
1000 V/us
1200 V
3V
300 mA
1000 V/us
1600 V
3V
300 mA
1000 V/us
2200 V
690 V
1000 A
131 W
860 kA2s
690 V
1000 A
131 W
860 kA2s
690 V
1000 A
131 W
860 kA2s
MECHANICAL AND THERMAL CHARACTERISTICS
Width
Depth
Height
Mass
Ta max Max amb. op. Temp.
Tstg
Storage temperature
500 mm
275 mm
855 mm
70 kg
40 °C
-40/60 °C
500 mm
275 mm
855 mm
70 kg
40 °C
-40/60 °C
500 mm
275 mm
855 mm
70 kg
40 °C
-40/60 °C
Document GOG9xx15T002