English
Language : 

GOG96010 Datasheet, PDF (1/3 Pages) Green Power Solutions srl – THREE PHASE AC-DC BRIDGE
Green Power Solutions srl
Via Greto di Cornigliano 6R - 16152 Genova , Italy
Phone: +39-010-659 1869
Fax: +39-010-659 1870
Web: www.gpsemi.it
E-mail: info@gpsemi.it
GOG96010
THREE PHASE AC-DC BRIDGE
Fuse protection
Blown fuse indicators with microswitch
Over temperature switches
Fan loss detection circuit
Snubber for SCR's protections
Extractible stacks for easy field service
LINE VOLTAGE UP TO 690V
DC OUTPUT CURRENT 1000A
Line to line voltage
GOG96010
690 V
Characteristic
IDC
DC output current
VINS (rms) Insulation voltage
Conditions
THYRISTOR CHARACTERISTICS
VGT
Gate trigger voltage
IGT
Gate trigger current
dV/dt
VRRM
Critical rate of rise off-state voltage
Blocking Voltage
Tj = 25 °C, VD = 5 V
Tj = 25 °C, VD = 5 V
Tj= 125 °C
Tj = 125 °C
FUSE TYPE SIBA 2067132.700
VNF
Rated voltage
INF
Rated current
PVF
Power loss
I²t
Total I2t
At rated current
MECHANICAL AND THERMAL CHARACTERISTICS
Width
Depth
Height
Mass
Ta max Max amb. op. Temp.
Tstg
Storage temperature
Value
1000 A
3000 V
2,5 V
250 mA
1000 V/us
2200 V
690 V
700 A
99 W
410 kA2s
500 mm
275 mm
655 mm
65 kg
40 °C
-40/60 °C
Document GOG96010T001