English
Language : 

GOG95034_17 Datasheet, PDF (1/3 Pages) Green Power Solutions srl – THREE PHASE AC-DC BRIDGE
Green Power Solutions srl
Via Venezia 34D - 10088 Volpiano (TO), Italy
Phone: +39-011-988 2251
Fax: +39-011-988 1358
Web: www.gpsemi.it
e-mail: info@gpsemi.it
GOG9xx34
THREE PHASE AC-DC BRIDGE
Fuse protection
Blown fuse indicators with microswitch
Over temperature switches
Fan loss detection circuit
Snubber for SCR's protections
Extractible devices for easy field service
LINE VOLTAGE UP TO 690V
DC OUTPUT CURRENT 3400A
Line to line voltage
GOG94034 GOG95034 GOG96034
400
500
690
Characteristic
IDC
DC output current
VINS (rms) Insulation voltage
Conditions
Value
3400 A
3000 V
Value
3400 A
3000 V
Value
3400 A
3000 V
THYRISTOR CHARACTERISTICS
VGT
Gate trigger voltage
IGT
Gate trigger current
dV/dt
VRRM
Critical rate of rise off-state voltage
Blocking Voltage
Tj = 25 °C, V D = 5 V
Tj = 25 °C, V D = 5 V
Tj= 125 °C
Tj = 125 °C
FUSE TYPE SIBA 2 x 2068132.1250
VNF
Rated voltage
INF
Rated current
PVF
Power loss
I²t
Total I2t
At rated current
At 660V
3V
500 mA
1000 V/us
1200 V
3V
500 mA
1000 V/us
1600 V
3V
500 mA
1000 V/us
2200 V
690 V
1250 A
147 W
1750 kA2s
690 V
1250 A
147 W
1750 kA2s
690 V
1250 A
147 W
1750 kA2s
MECHANICAL AND THERMAL CHARACTERISTICS
Width
Depth
Height
Mass
Ta max Max amb. op. Temp.
Tstg
Storage temperature
780 mm
470 mm
1150 mm
260 kg
40 °C
-40/60 °C
780 mm
470 mm
1150 mm
260 kg
40 °C
-40/60 °C
780 mm
470 mm
1150 mm
260 kg
40 °C
-40/60 °C
Document GOG9xx34T001