English
Language : 

GOG91K48 Datasheet, PDF (1/3 Pages) Green Power Solutions srl – THREE PHASE AC-DC BRIDGE
Green Power Solutions srl
Via Greto di Cornigliano 6R - 16152 Genova , Italy
Phone: +39-010-659 1869
Fax: +39-010-659 1870
Web: www.gpsemi.it
E-mail: info@gpsemi.it
GOG91K48
THREE PHASE AC-DC BRIDGE
Fuse protection
Blown fuse indicators with microswitch
Over temperature switches
Fan loss detection circuit
Snubber for SCR's protections
Extractible stacks for easy field service
LINE VOLTAGE UP TO 1000V
DC OUTPUT CURRENT 4800 A
Line to line voltage
GOG91K48
1000 V
Characteristic
IDC
DC output current
VINS (rms) Insulation voltage
Conditions
1 min. (IEC 1461.1)
THYRISTOR CHARACTERISTICS
VGT
Gate trigger voltage
IGT
Gate trigger current
dV/dt
VRRM
Critical rate of rise off-state voltage
Blocking Voltage
Tj = 25 °C, VD = 5 V
Tj = 25 °C, VD = 5 V
Tj= 125 °C
Tj = 125 °C
FUSE TYPE: 4 x SIBA 2078132.800
VNF
Rated voltage
INF
Rated current
PVF
Power loss
I²t
Total I2t
At rated current
At 1000 V
MECHANICAL AND THERMAL CHARACTERISTICS
Width
Depth
Height
Mass
Ta max Max amb. op. Temp.
Tstg
Storage temperature
Value
4800 A
3000 V
3V
400 mA
1000 V/us
2800 V
1250 V
800 A
135 W
1070 kA2s
802 mm
495 mm
1420 mm
220 kg
40 °C
-40/60 °C
Document GOG91K48T001