e-mail: info@gpsemi.it
GOB96017
BI-DIRECTIONAL
THREE PHASE AC-DC BRIDGE
Fuse protection
Blown fuse indicators with microswitch
Over temperature switches
Fan loss detection circuit
Snubber for SCR's protections
Extractible stacks for easy field service
LINE VOLTAGE UP TO 690V
DC OUTPUT CURRENT 1700A
Line to line voltage
GOB96017
690 V
Characteristic
IDC
DC output current
VINS (rms) Insulation voltage
Conditions
THYRISTOR CHARACTERISTICS
VGT
Gate trigger voltage
IGT
Gate trigger current
dV/dt
VRRM
Critical rate of rise off-state voltage
Blocking Voltage
Tj = 25 °C, V D = 5 V
Tj = 25 °C, V D = 5 V
Tj= 125 °C
Tj = 125 °C
FUSE TYPE SIBA 2077132.500
VNF
Rated voltage
INF
Rated current
PVF
Power loss
I²t
Total I2t
At rated current
At 1000V
MECHANICAL AND THERMAL CHARACTERISTICS
Width
Depth
Height
Mass
Ta max Max amb. op. Temp.
Tstg
Storage temperature
Value
1700 A
3000 V
3V
300 mA
1000 V/us
2200 V
1000 V
500 A
90 W
310 kA2s
620 mm
420 mm
1409 mm
170 kg
40 °C
-40/60 °C