English
Language : 

GOB94018 Datasheet, PDF (1/3 Pages) Green Power Solutions srl – BI-DIRECTIONAL THREE PHASE AC-DC BRIDGE
Green Power Solutions srl
Via Greto di Cornigliano 6R - 16152 Genova , Italy
Phone: +39-010-659 1869
Fax: +39-010-659 1870
Web: www.gpsemi.it
E-mail: info@gpsemi.it
GOB9xx18
BI-DIRECTIONAL
THREE PHASE AC-DC BRIDGE
Fuse protection
Blown fuse indicators with microswitch
Over temperature switches
Fan loss detection circuit
Snubber for SCR's protections
Extractible stacks for easy field service
LINE VOLTAGE UP TO 690V
DC OUTPUT CURRENT 1800 A
Line to line voltage
GOB94018 GOB95018
400 V
500 V
Characteristic
IDC
DC output current
VINS (rms) Insulation voltage
Conditions
Value
1800 A
3000 V
Value
1800 A
3000 V
THYRISTOR CHARACTERISTICS
VGT
Gate trigger voltage
IGT
Gate trigger current
dV/dt
Critical rate of rise off-state voltage
VRRM
Blocking Voltage
Tj = 25 °C, VD = 5 V
Tj = 25 °C, VD = 5 V
Tj= 125 °C
Tj = 125 °C
FUSE TYPE SIBA 2068132.1250
VNF
Rated voltage
INF
Rated current
PVF
Power loss
I²t
Total I2t
At rated current
At 660V
3V
300 mA
1000 V/us
1200 V
3V
300 mA
1000 V/us
1600 V
690 V
1250 A
147 W
1750 kA2s
690 V
1250 A
147 W
1750 kA2s
MECHANICAL AND THERMAL CHARACTERISTICS
Width
Depth
Height
Mass
Ta max Max amb. op. Temp.
Tstg
Storage temperature
500 mm
375 mm
1405 mm
130 kg
40 °C
-40/60 °C
500 mm
375 mm
1405 mm
130 kg
40 °C
-40/60 °C
Document GOB9xx18T002