English
Language : 

GOA94002W_17 Datasheet, PDF (1/2 Pages) Green Power Solutions srl – THREE PHASE AC-SWITCH
Green Power Solutions srl
Via Venezia 34D - 10088 Volpiano (TO), Italy
Phone: +39-011-988 2251
Fax: +39-011-988 1358
Web: www.gpsemi.it
e-mail: info@gpsemi.it
GOA9xx02W
THREE PHASE AC-SWITCH
Fuse protection
Temperature sensors
Snubber for SCR's protections
Water cooling
Lowest overall dimensions
LINE VOLTAGE UP TO 500V
OUTPUT PHASE CURRENT 250A
Line to line voltage
GOA940… GOA950…
400
500
Characteristic
IRMS
Output phase current
VINS (rms) Insulation voltage
Conditions
THYRISTOR CHARACTERISTICS
VGT
Gate trigger voltage
IGT
Gate trigger current
dV/dt
VRRM
Critical rate of rise off-state voltage
Blocking Voltage
Tj = 25 °C, V D = 5 V
Tj = 25 °C, V D = 5 V
Tj= 125 °C
Tj = 125 °C
FUSE TYPE SIBA 2041220.200
VNF
Rated voltage
INF
Rated current
Value
250 A
3000 V
Value
250 A
3000 V
3V
300 mA
1000 V/us
1200 V
3V
300 mA
1000 V/us
1600 V
690 V
200 A
690 V
200 A
MECHANICAL AND THERMAL CHARACTERISTICS
Width
Depth
Height
Mass
Tw max Max water Temp.
Tstg
Storage temperature
240 mm
119 mm
384 mm
20 kg
30 °C
-40/60 °C
240 mm
119 mm
384 mm
20 kg
30 °C
-40/60 °C
Document GOA9xx02WT001