English
Language : 

C3169 Datasheet, PDF (1/1 Pages) General Cable Technologies Corporation – 2C 16 19/.0117 BC OAS FLEX PVDF TYPE CL2P / CMP
Product Data Sheet
Part Number: C3169
Revision Level:
0
Date:
7/7/2007
2C 16 19/.0117 BC OAS FLEX PVDF
TYPE CL2P / CMP
A. CONSTRUCTION
DIAMETERS
Conductor:
Insulation:
Cable:
Jacket:
Print Legend:
#16 AWG 19/.0117 Bare Copper
0.059” nom.
0.007" Wall FLEXGUARD*
0.073" nom.
2 conductors @ 3.50” LHL w/ AL/Polypro (foil out)
0.161" nom.
0.010"Wall PVDF – Natural
0.181" +/- 0.009"
-Plenum ripcord under jacket.
CAROL (R) 16 AWG -- C3169 -- 60C E60233-8 CL2P OR CMP(UL) C(UL) -- MADE IN USA
DATE CODE (PRINT EVERY 2 FT)
B. INDUSTRY APPROVALS
National Electrical Code
UL Standard 13
Article 725
Type CL2P
National Electrical Code
UL Standard 444
C. ELECTRICAL PROPERTIES
TEMPERATURE:
SUGGESTED WORKING VOLTAGE (Vrms):
CONDUCTOR D.C. RESISTANCE:
Article 800
Type CMP
60C
150 Vrms (CL2P)
4.1 Ohms/1000 ft. nom. @ 20C
D. COLOR CODE (Listed as Individual Conductors or Pairs of Conductors)
1 Black
2 White
Note: Data are subject to change without notice. Contact your Customer Service representative for latest information.