English
Language : 

C3135 Datasheet, PDF (1/1 Pages) General Cable Technologies Corporation – 2C 12 19/.0185 BC FLEX PVDF TYPE CL2P / CMP
Product Data Sheet
Part Number: C3135
Revision Level:
0
Date:
7/7/2007
2C 12 19/.0185 BC FLEX PVDF
TYPE CL2P / CMP
A. CONSTRUCTION
DIAMETERS
Conductor:
Insulation:
Cable:
Jacket:
Print Legend:
#12 AWG 19/.0185 Bare Copper
0.089” nom.
0.010" Wall FLEXGUARD*
0.109" nom.
2 Conductors @ 4.00" LHL.
0.218" nom.
0.010"Wall PVDF – Natural
0.238" +/- 0.012"
-Plenum ripcord under jacket.
CAROL (R) 12 AWG -- C3135 -- 60C E60233-8 CL2P OR CMP(UL) C(UL) -- MADE IN USA
DATE CODE (PRINT EVERY 2 FT)
B. INDUSTRY APPROVALS
National Electrical Code
UL Standard 13
Article 725
Type CL2P
National Electrical Code
UL Standard 444
C. ELECTRICAL PROPERTIES
TEMPERATURE:
SUGGESTED WORKING VOLTAGE (Vrms):
CONDUCTOR D.C. RESISTANCE:
Article 800
Type CMP
60C
150 Vrms (CL2P); 300 Vrms (CMP)
1.6 Ohms/1000 ft. nom. @ 20C
D. COLOR CODE (Listed as Individual Conductors or Pairs of Conductors)
1 Black
2 White
Note: Data are subject to change without notice. Contact your Customer Service representative for latest information.