English
Language : 

C1648A Datasheet, PDF (1/1 Pages) General Cable Technologies Corporation – CONTROL CABLE
Product Data Sheet
Part Number: C1648A
Revision Level:
6
Date:
9/18/2007
8C 20 AWG 26/34 TC PE OAS PVC
CONTROL CABLE
A. CONSTRUCTION
DIAMETERS
Conductor:
Insulation:
Cable:
Braid
Jacket:
Print Legend:
#20 AWG 26/34 Tinned Copper
0.038" nom.
0.016" Wall Polyethylene
0.068" nom.
8 conductors @ 3.00" LHL with aluminum/
0.230" nom.
polyester (foil out)
#34 AWG Tinned Copper
0.258" nom.
75% Min. coverage
0.029" Wall Polyvinyl Chloride
0.316" +/- 0.016"
CAROL (R) 20 AWG -- C1648A -- 75C E60233-8 (UL) CL2 OR AWM STYLE 2094 -- MADE IN
USA (DATE CODE)
B. INDUSTRY APPROVALS
National Electrical Code
UL Standard 13
Article 725
Type CL2
UL Standard 758
C. ELECTRICAL PROPERTIES
TEMPERATURE:
SUGGESTED WORKING VOLTAGE (Vrms):
CONDUCTOR D.C. RESISTANCE:
MUTUAL CAPACITANCE:
GROUND CAPACITANCE:
AWM Style 2094
75 C
300Vrms
11.3 Ohms/1000 ft nom
20 pF/ft @ 1kHz nom
36 pF/ft @ 1kHz nom
D. COLOR CODE (Listed as Individual Conductors or Pairs of Conductors)
1 Black
2 White
3 Red
4 Green
5 Yellow
6 Blue
7 Brown
8 Orange
Note: Data are subject to change without notice. Contact your Customer Service representative for latest information.