English
Language : 

EN55022 Datasheet, PDF (2/7 Pages) General Semiconductor – CAR2512FP series rectifier Input: 90Vac to 264Vac Output: 12Vdc 208A 3.3Vdc or 5 Vdc 1A
GE Energy
CAR2512FP series rectifier
Input: 90Vac to 264Vac; Output: 12 Vdc @ 208A; 3.3Vdc or 5 Vdc @ 1A
Absolute Maximum Ratings
Stresses in excess of the absolute maximum ratings can cause permanent damage to the device. These are absolute stress ratings only, functional
operation of the device is not implied at these or any other conditions in excess of those given in the operations sections of the data sheet.
Exposure to absolute maximum ratings for extended periods can adversely affect the device reliability.
Parameter
Device
Symbol
Min
Max
Unit
Input Voltage: Continuous
Operating Ambient Temperature
All
VIN
0
264
Vac
All
TA
-10
701
°C
Storage Temperature
All
Tstg
-40
85
°C
I/O Isolation voltage to Frame (100% factory Hi-Pot tested)
All
1500
Vac
Electrical Specifications
Unless otherwise indicated, specifications apply over all operating input voltage, load, and temperature conditions.
INPUT
Parameter
Device Symbol
Min
Typ
Operational Range
All
VIN
Frequency Range
(ETSI 300-132-1 recommendation)
All
FIN
Main Output Turn_OFF
All
VIN
90
110/230
47
50/60
Maximum Input Current
(VO= VO, set, IO=IO, max)
VIN= 100Vac
All
VIN= 180Vac
IIN
Cold Start Inrush Current
(Excluding x-caps, 25C, <10ms, per ETSI 300-132)
All
IIN
Efficiency
100% load
91.6
(Tamb=25C, Vin = 230V, Vout= 12V, IO, max)
50% load
All

20% load
92.5
90
Power Factor
(Vin=230Vac, IO=IO, max)
All
PF
0.99
Holdup time2
(Vout= 12Vdc, Tamb 25C, IO=IO, max)
Vin= 230Vac
Vin= 100Vac
All
T
12
15
Early warning prior to output falling below regulation
All
2
Ride through
All
T
10
Leakage Current
(Vin= 250Vac, Fin = 60Hz)
All
IIN
3
Isolation
Input/Output
3000
Input/Frame
All
1500
Output/Frame
100
Max
264
63
80
14.3
16
40
Unit
Vac
Hz
Vac
Aac
Apeak
%
ms
ms
ms
mArms
Vac
Vac
Vdc
12Vdc MAIN OUTPUT
Parameter
Device Symbol
Min
Output Power
HL / LL [180 – 264 / 90-132 Vac] Vdc ≥ 12Vdc
All
W
0
Vdc = 10.8Vdc
0
Set point
All
11.9
Overall regulation (load, temperature, aging)
Ripple and noise3
All
-3
All
Vout
Turn-ON overshoot
All
Turn-ON delay
All
T
Typ
-
-
12.00
Max
2500/1200
2246/1078
12.1
+3
120
+3
2
Unit
W
W
Vdc
%
mVp-p
%
sec
1 Derated above 50C at 2.5%/C
2 12V output can decay down to 10.8V
3 Measured across a 10µf electrolytic and a 0.1µf ceramic capacitors in parallel. 20MHz bandwidth
July 18, 2012
©2012 General Electric Company. All rights reserved.
Page 2