MB-G6-12-R Datasheet, PDF (2/2 Pages) Gamewell-FCI by Honeywell – Wheelock MB Series Motor Bells
Ordering Information
MODEL SHELL
NUMBER SIZE
MB-G6-12-R 6"
MB-G6-24-R 6"
MB-G10-12-R 10"
MB-G10-24-R 10"
INPUT
VOLTAGE
(VDC)
12
24
12
24
INPUT
CURRENT
0.060
0.030
0.060
0.030
NOTES:
1. Typical dBA at 10 feet is 92, measured in an
anechoic chamber.
2.Mounting options are: D,E,J,K,N,R,S,Z
3. For bells at 12 VDC models are UL rated for 9.0 to
15.6 VDC and all 24 VDC models for 18.0 to 31.0
MODEL
NUMBER
RSSP-24MCW-FR
RSSP-241575W-FR
RSSP-121575W-FR
NOMINAL
VOLTAGE
(VDC)
24
24
12
STROBE
CANDELA
AVERAGE CURRENT
(amps) @ LISTED
VDC
15/30/75/110 .050/.081/.133/.161
15 (75 on axis)
0.065
15 (75 on axis)
0.170
1. Mounting options are: D,E,Z
2. Average current per actual Wheelock product testing at listed VDC.
For rated average and peak current across UL regulated voltage range
for both filtered DC and unfiltered VRMS, see Installation instructions.
SYNC MODELS/POWER SUPPLY
M ODEL
NUM BER
SM-12/24-R
INP UT
VOLT A GE
(VDC)
24
AVERAGE
M EAN
C UR R EN T
@ 24 VDC
.028
M OUNTING
OP TIONS**
W
DSM-12/24-R
24
.035
W
SM Sync Module is rated for 3.0 amperes @ 24VDC.
DSM Sync Module is rated for 3.0 amperes per circuit. The maximum number of
interconnected DSM modules is twenty (20).
** Refer to mounting options data sheet.
Wiring Diagram
Fig. 1 Bell Models
+-
FROM
{ P R E C E D IN G
APPLIANCE
OR FACP
Fig. 2 Retrofit Strobe
AUDIBLE
+-
TO NEXT
} APPLIANCE
OR END-OF-LINE
RESISTOR
(EOLR)
FROM
P R E C E D IN G
- APPLIANCE OR
+ F A C P
FROM
P R E C E D IN G
STROBE OR
FACP
-
+
STROBE
+-
- TO NEXT
+ APPLIANCE
OR EOLR
- TO NEXT
+ STROBE OR
EOLR
Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed,
operated, maintained and operationally tested in accordance with their installation instructions at the time of installation and at
least twice a year or more often and in accordance with local, state and federal codes, regulations and laws. Specification,
application, installation, operation, maintenance and testing must be performed by qualified personnel for proper operation in
accordance with all of the latest National Fire Protection Association (NFPA), Underwriters’ Laboratories (UL), National Electrical
Code (NEC), Occupational Safety and Health Administration (OSHA), local, state, county, province, district, federal and other
applicable building and fire standards, guidelines, regulations, laws and codes including, but not limited to, all appendices and
amendments and the requirements of the local authority having jurisdiction (AHJ).
The Gamewell Company
12 Clintonville Road
Northford, CT 06472-1610
Phone: 203-484-7161
Fax: 203-484-7118
www.gamewell.com
A Honeywell Company
© 2004 Gamewell
WARNING
PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS
CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COM-
PLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN
IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN
EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS
INJURY OR DEATH TO YOU AND/OR OTHERS.
Specifications and wiring information are provided for information only and are believed
to be accurate. Gamewell assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring
instructions shipped with the product shall always be used for actual installation. For
more information, contact Gamewell.
Page 2 of 2
MB Series Motor Bells CS-2236 05/04/04