DIMENSIONAL DATA
INSTALLATION
Installation is simple because of the non-polarized
connection. The detector mounts to the base by a
twist-to-lock action. A removable locking tab secures
the head to the base to provide a degree of vandal
resistance. Units mount directly on a 3-inch round box,
3, 3.5 or 4-inch octagonal box, and 4-inch square box.
No adapters required.
NOTE: The number of two-wire smoke detectors
which can be accommodated per zone varies with the
different control panels. Consult the control panel
instruction manual to determine the capacity.
Refer to N.F.P.A. 72, Chapter 5-3 “Smoke Sensing
Fire Detectors” for spacing, location of detectors and
other guidelines.
MAINTENANCE
Cleaning programs should be adapted to the
individual environment in conformance with NFPA
Standard 72. We recommend, at the least, an annual
cleaning of dust from the detector head by using the
suction from a vacuum cleaner. Refer to the
installation instructions for the complete
procedure.
WARNING: To prevent detector contamination
during construction, smoke detectors must be
protected from dust and contamination until the
area is clean and dust free. See NFPA 72
CAUTION: Do not attempt disassembly of the
factory sealed smoke detector. This assembly
is sealed for your protection and is not to be
opened for servicing. Opening of the detector
will void the warranty.
TABLE I
DETECTOR BASE OPTIONS
Model
2-Wire
2WRLT
2WRB
4WRB
Compatibility
Identifier
FE51A
FE52A
FE55A
N/A
Description
Connects to 2-wire detection circuit via screw terminals.
As above except has output for remote test and LED indicator.
Connects to 2-wire detection circuit via wire-leads.
Has remote test feature, LED indicator and SPDT auxiliary relay
rated 1 amp. @ 30 VDC. Minimum alarm current: .019 amp.
(maximum of 1 per zone)
Connects to 4-wire detection circuit via wire-leads.
Equipped with SPDT auxiliary relay rated 2 amp. @ 30 VDC.
Minimum alarm current .015 amp.
TABLE II
ORDERING INFORMATION
Model
CPD-7051
MA-001
2WRM
4WRM
2040-24
RAI-2
RCM-500
Compatibility
Identifier
I51FE1
Description
Ionization smoke detector.
Adapter to allow mounting to existing CPD series bases.
Relay component of 2WRB.
Relay component of 4WRB
End of line supervisory relay, 24 VDC.
Remote alarm indicator.
Remote alarm indicator /key test switch.
Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed
by Gamewll-FCI for their use. Specifications subject to change without notice.