English
Language : 

AAD-9400X Datasheet, PDF (2/2 Pages) Gamewell-FCI by Honeywell – Intelligent Fire Alarm Aspiration Sensing Technology
Specifications
Intelligent FAAST XT Specifications
Electrical Specifications
External Supply Voltage 18-30 VDC
Remote Reset Time External monitor must be pulled
low for a minimum of 100 ms
Power Reset
1 sec.
Avg. Operating Current Fan High - 465mA, 11.2W;
Fan Med - 340mA, 8.2W;
Fan Low - 220mA, 5.3W
Alarm
Fan High - 493mA, 11.85W;
Fan Med - 368mA, 8.85W;
Fan Low - 248mA, 6W
Relay Contact Ratings 3.0 A @ 30 VDC,
0.5 A @ 125 VAC
Environmental Ratings
Operating Temperature 32°F (0°C) to 100°F (38°C);
Factory Tested to 133°F (55°C)
Sampled Air
Temperature
-4°F (-20°C) to 140°F (60°C)
Humidity Range
10 to 95% (non-condensing)
IP Rating
IP30
Coverage Area
28,800 sq.ft. (2,676 sq.m)
Air Movement
0-4,000 ft./min. (0-1,219 m/min.)
Physical Specifications
Height
13.3 in (338 mm)
Width
13.1 in (333 mm)
Depth
7.5 in (191 mm)
Cable Access
4 1-inch (2.54 cm) cable entry
holes on top, bottom and back of
the unit
Wire Gauge
12 AWG (2.05 mm) max. to
24 AWG (0.5 mm) min.
Maximum Single Pipe
Length
400 ft. (123 m)
Total Pipe Length
1050 ft. (320 m)
(*all designs must be verified
within PipeIQ software)
Multiple Pipe Network 262 ft. per pipe
Network Outside Pipe
Diameter
1.050 inches, IPS (25 mm)
Internal Pipe Diameter 0.591 to 0.827 inches (15-21 mm)
Sensitivity Range
0.00046%Obs/ft to 6.25% Obs/ft
(0.0015% Obs/m to 20.5% Obs/m)
Relays
8 Form C, 3 AMP, programma-
ble latching or non-latching
Diagnostic Specifications
Event Log
18,000 events stored
Trend Data Log
Configurable sampling period
(1 minute to 1 day)
Service Log
300 custom user entries
Network Specifications
Communication
Network
Ethernet monitoring
6 E-mail address alerts,
TCP and Serial Modbus
Network Services
DHCP, SMTP, HTTP, MODBUS/
TCP, AutoIP, NetBIOS-NS,
Serial MODBUS
Ethernet
10/100Mbps, MDI-X
Modbus
TCP or Serial RS-
Email
6 recipients, sel. notification
Specifications (Continued)
Network Specifications (Continued)
Webserver
Read Configuration, Live View,
Logs
Configuration Specifications
PipeQ
USB or Ethernet
Modbus
Ethernet or RS-485
Figure 1 illustrates the FAAST XT user interface display.
Figure 1 - Intelligent FAAST XT User Interface Display
The User Interface consists of 5 Alarm levels:
• Alert
• Fire 1 and Fire 2, 10 Particulate levels
• Action 1
and Flow and Fault graph
• Action 2
Ordering Information
Part Number Description
AAD-9400X System Sensor Intelligent FAAST XT Fire
Alarm Aspiration Sensing Technology
Accessories
CMKT00100 FAAST Information Kit–Includes a
Comprehensive Instruction Manual
F-A3384-000 Replacement Air Filter Assembly
Various†
UL®-Approved Pipe and Fittings
† Additional accessory information, including part num-
bers, can be accessed at systemsensor.com/faast.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9021-60838 Rev. A page 2 of 2