English
Language : 

72223-160 Datasheet, PDF (2/2 Pages) Gamewell-FCI by Honeywell – Reflective Beam Smoke Detector
Operational Specifications
Fault condition (trouble).
90% or more obscuration.
Automatic gain control limit.
Improper initial alignment.
Integral alignment aid: prism targeting mode.
Alarm indicator: red LED.
Trouble indicator: green LED.
Ordering Information
72223-160
72223-330
72224
Reflective beam smoke detector, 160 ft. (48.768 m) (50R).
Reflective beam smoke detector, 330 ft. (100 m) (100R).
Replacement prism.
Specifications
Primary input power
10 to 30 VDC maximum.
Standby
0.004 A maximum.
Alarm current
0.014 A maximum.
Relay contacts
0.5 A at 30 VAC/VDC.
Reset time
5 seconds maximum.
Standby current
0.040 A.
Start-up time
10 seconds.
Optical wavelength
880 nm.
Temperature rating
—22°F to 131°F (—30°C to 55°C).
Relative humidity
10 to 93% RH non-condensing.
Dimensions
8.25" H x 4.5" W x 4.75" D (cm: 21.0 H
x 11.43 W x 12.065 D).
Finish
Gray/black.
Weight
1.5 lbs. (0.68 kg).
Range
15 ft. to 330 ft. (m: 5 to 100).
The Gamewell Company
12 Clintonville Road
Northford, CT 06472-1610
Phone: 203-484-7161
Fax: 203-484-7118
www.gamewell.com
A Honeywell Company
© 2004 Gamewell
Specifications and wiring information are provided for information only and are
believed to be accurate. Gamewell assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring
instructions shipped with the product shall always be used for actual installation.
For more information, contact Gamewell.
Page 2 of 2
Reflective Beam CS-2154 06/23/04