Engineer Specifications
All models shall have a sound output of 83 dBA at 10 feet and a listed frequency response rate of 800 to 1200 Hz. All inputs
shall employ terminals that accept #12 to #18 AWG wire sizes. The strobe portion of the appliance shall produce a flash
rate of one (1) flash per second over the Regulated Input Voltage Range of 16 to 33 VDC for 24 VDC models and shall
incorporate a Xenon flashtube enclosed in a rugged Lexan ® lens. The strobe shall be of low current design and shall
have Zero Inrush. The strobe intensity shall have a minimum of four (4) field selectable settings and shall be rated per UL
1971 for: 15, 30, 75 or 110 candela (wall mount versions). The switch for selecting the candela setting shall be located on
the rear of the appliance in order to prevent tampering from unauthorized persons. When synchronization is required, the
strobe portion of the appliance shall be compatible with the SM, DSM sync modules or FF8 Power Supply. The strobes
shall not drift out of synchronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e.,
contacts remain closed), the strobe shall revert to a non-synchronized flash rate. The chime and the chime strobe
appliances shall be designed for indoor surface or flush mounting. The Chime Strobe shall be Gamewell MOdel 72041
or 72042.
Specifications
Part No. Model
Strobe
Candela
Anechoic
Peak dBA @10’
72041
CH70-24MCW-FR 15/30/75/110
83
72042
CH70-24MCW-FW 10/30/75/110
83
71761
CH70-241575W-FR 15/75
83
* Multi-candela Average Strobe Current @ 24VDC
15CD 30CD 75CD 110CD
.047 .081 .128 .166
dBA @10’
Rated
Reverberant Current
Min Max
52
58
*.020 Chime Only
52
58
*.020 Chime Only
52
58
.085
Notes:
• Strobes are designed to flash at 1 flash per second minimum from 20-31VDC. Note that NFPA-72
(1999) specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1
to 3 flashes per second.
• All candela ratings represent minimum effective strobe intensity based on UL 1971.
• Series CH Strobe products are UL 1971 for indoor use with a temperature range of 32o F to 120o F
(0oC to 49oC) and maximum humidity of 85%.
Ordering Information
Part Number
Description
CH Series provide Synchronized Strobe with 71548 or 71549 Sync Modules
72041
Selectable Candela Chime Strobe, Wall Mount, 24VDC, Red (CH70-24MCW-FR)
72042
Selectable Candela Chime Strobe, Wall Mount, 24VDC, White (CH70-24MCW-FW)
71761
15/75CD Chime Strobe, .065 Amp, Wall Mount, 24VDC, Red (CH70-241575W-FR)
Mounting Accessories for CH Series Chime Strobes
BO*
4” Sq. Deep w/Extension Ring
70418
Backbox, Surface Mount, 5-1/2" x 5-9/16" x 3-9/16", Red (SBB-R)
71643
Backbox, Surface Mount, 10-15/16" x 6-7/64" x 1-11/16", Red (SBL2-R)
68292
Plate, Semi-Flush, 6" Square x 5/16"D, Red (SFP-R)
71317
Molded Extender, 5-1/4" Square x 25/32"D, Red (ISP-R)
71318
Retrofit Plate, 8" x 5-7/8" x 13/32", Red (RP-R)
BO*
Items purchased by others. For more details, refer to CS-2248.
Specifications and wiring information are provided for information only and are believed to be accurate. Gamewell assumes no
responsibility for their use. Data and design are subject to change without notice. Installation and wiring instructions shipped with the
product shall always be used for actual installation. For more information, contact Gamewell.
The Gamewell Company
60 Pleasant St.
Ashland, MA 01721
Made in the USA
Voice (508) 231-1400
888-FIREBOX • (888) 347-3269
FAX (508) 231-0900
www.gamewell.com
Gamewell 2002
CS-2245 Rev. 1102-6
Page 2