7100-1-PNL Datasheet, PDF (2/3 Pages) Gamewell-FCI by Honeywell – Compact Analog Addressable Fire Alarm Control Panel
•
Optional Accessories
LCD-7100
The LCD-7100 remote serial display offers an 80-character
alphanumeric readout for the remote display of all system
events. It duplicates all the information on the 7100 Series
panel display and provides key switch protected functions
such as System Reset, Alarm Acknowledge, Trouble
Acknowledge, Signal Silence, and Drill Test.
LEDs on the LCD-7100 indicate Alarm, Supervisory, Sys-
tem Trouble, Power Fault, Systems Silenced, NAC#1, and
NAC#2 Silenced conditions.
The LCD-7100 can be surface or semi-flush mounted on a
standard four-gang electrical box. It can be installed up to
3,000 feet (914.4 m) from the main control panel. The 7100
Series fire alarm control panel supports up to five remote
LCD-7100 annunciators using one pair of twisted, non-
shielded 18 AWG min. wire or serial communication and
uses another pair of 16 AWG min. for operating voltage.
(For additional information, refer to the LCD-7100 data
sheet, Part Number: 9020-0486).
RAN-7100
The RAN-7100 maintains the same character display as
the 7100 Series. The RAN-7100 is mounted in a RAN2-BB
backbox for surface or flush mounting retrofits.
(For additional information, refer to the Gamewell Retrofit
Kits Data Sheet, P/N: 9020-60678).
CAOM
The Class “A” Optional Module (CAOM) allows Style Y and
Z (Class “B” and “A”) operation for both Notification Appli-
ance Circuits and allows Style 4 and 6 (Class “B” and “A”)
for the Signaling Line Circuit. It also provides a disconnect
switch for the signaling line circuit and a common discon-
nect switch for both notification appliance circuits.
MCOM
The Municipal Connection Option Module (MCOM) pro-
vides three choices of outputs. It can be configured as a
Municipal Circuit (City Box) output. It may also be set to
serve as a Reverse Polarity output with a nominal voltage
output of 24 VDC at 0.012 amp maximum alarm and
supervisory current. The MCOM’s third option provides a
releasing solenoid output rated at:
• 24 VDC nominal voltage.
• 0.005 amp supervisory current.
• 0.710 amp maximum alarm current.
• 2 ohms maximum line resistance.
PTRM
The Printer Transient Module (PTRM) provides RS-232
Isolator/Transient protection for the 7100’s RS-232 port
(BSM connector J2). It is used in conjunction with a serial
printer applied to the RS-232 port for permanent record
keeping.
INI-7100
The Intelligent Network Interface Module allows the 7100
Series fire alarm control panel to become the platform of a
peer-to-peer, token ring, self-regenerative network com-
prised of up to 64, 7100 panels.
Features (Continued)
• Four levels of system access using six digit passwords
with up to five user passwords per Level.
• Duplicate and extra address indications.
• March time (60 or 120 BPM)/temporal pattern/coded
fours/California Code/user-defined zone coding.
• Cross zoning.
• System configuration programming and 280 event log
stored in non-volatile memory.
• Fan restart with sequential restart delay.
• Upload/download of panel configuration between panel
and CAMWorks program (password protected feature).
• Up to 64, 7100 panels in the E3 Broadband network
with an optional INI-7100 Module.
Specifications
Primary Input Power 120 VAC, 50/60 Hz @ 2.0 amps.
or 240 VAC, 50/60 Hz @ 1.0 amp
Output Power
3.335 amps. @ 24 VDC (total)
Non-resettable Power: 1.0 amp max.
Resettable Power: 1.0 amp max.
1.0 amp max. from both power
circuits
Two Notification
Appliance Circuits: 1.5 amp each @ 24 VDC
Current:
Supervisory Alarm
7100-1 (One SLC) 0.065 amp
0.085 amp
7100-1D
(One SLC w/DACT) 0.075 amp
0.095 amp
LCD-7100
0.050 amp
0.075 amp
INI-7100-UTP,-FO 0.040 amp
0.040 amp
Operating
Temperature:
32° - 120° F (0° - 49° C)
Relative Humidity: 93 % (non-condensing)
Battery Charger
Capacity:
31 A/H (Cabinet accommodates
12 A/H size batteries)
Alarm & Trouble
Relay Contacts:
Form “C”, 2 amps. @ 24 VDC
(resistive)
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9020-0466 Rev. N page 2 of 3