XP95-ID Datasheet, PDF (1/2 Pages) Gamewell-FCI by Honeywell – Analog Addressable Duct Smoke Detectors
XP95-PD/-PDR,
XP95-ID/-IDR
Description
The Gamewell-FCI analog addressable duct smoke detec-
tors provide early detection of smoke and products with
combustion present in air moving through an HVAC duct.
Fans, blowers and complete systems may be shut down or
activated in fire alarm mode by the Fire Alarm Control
Panel (FACP) in the event of smoke detection.
Analog Addressable Duct
Smoke Detectors
The Gamewell-FCI analog addressable duct smoke detec-
tors may utilize either interchangeable photoelectric or ion-
ization sensor heads. The external alarm indication is a
light-emitting diode (LED), easily visible through the hous-
ing. A manual reset switch is provided on the front of the
sensor.
Duct smoke detectors are also available with auxiliary relay
contacts. The relay requires two additional wires for power
and will activate when the sensor reaches alarm levels. All
wiring must comply with local codes and regulations.
XP95 Duct Smoke Detectors digitally transmit their address
and the chamber’s analog value to the FACP for analysis.
Air sampling is accomplished by two tubes which protrude
into the duct. An exhaust tube of one standard length 7.5"
(19.05 cm) is provided with the sensor housing. Intake sam-
pling tubes, which must be ordered separately, are supplied
in three standard lengths: 2.5, 5, or 10 feet
(0.762, 1.524, or 3.048 m).
Installation
Duct mounting is accomplished by the use of a template
and four sheet metal screws, provided. The duct detectors
are compatible with the analog loops on Gamewell-FCI’s
600 Series Analog Addressable Control Panels.
Features
XP95 Series
• Compatible with the Gamewell-FCI 600 Series analog
addressable control panels
• Interchangeable “Plug-in” photoelectric or ionization
heads
• Address is stored in the sensor base
• Address is set by XPert addressing card
• Remote alarm LED option
• Two-wire supply- polarity insensitive
• Very low standby current
• LED alarm indication on sensor head
• Rugged steel backbox with clear plastic cover
• Large terminal connection screws
• No additional screens or filters to clean or replace
• Relay version available with optional remote test unit
• Three standard tube lengths available: 2.5, 5, or 10 ft.
(0.762, 1.524, or 3.048 m)
Programming
The only programming required for the XP95 Duct Smoke
Sensors is address setting. This is accomplished through
the use of the XPert addressing card which is inserted into
the sensor base.
An ISO 9000-2000 Company
SIGNALING
268A
FM MEA
Approved
APPROVED 73-92-E 3242-1004:103 (photo)
3242-1004:102 (ion)
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2007 by Honeywell International Inc. All rights reserved.
www.gamewell-fci.com
CS-2049 Rev. a1 page 1 of 2