English
Language : 

SS-F Datasheet, PDF (1/2 Pages) Gamewell-FCI by Honeywell – Filtrex Hostile Area Smoke Head Analog Addressable Detector with SmartScan
SS-F
Filtrex™ Hostile-Area Smoke Head —
Analog Addressable Detector with SmartScan™
SS-F Operation Overview
Description
Gamewell’s SS-F SmartScan™
smoke detector provides early
warning smoke detection in
hostile environments where tra-
ditional smoke detectors are not
practical. Using a small air in-
take fan and a high-perfor-
mance replaceable filter, air and
smoke are drawn into a photo-
electric sensing chamber, while
unwanted airborne particulate
and water mist are removed.
This feature allows the SS-F to
operate in difficult applications,
such as textile or paper mills,
which due to environmental
conditions tend to cause nui-
sance alarms with standard
smoke detectors.
Normal Operation — A miniature fan is pulsed on and off under microprocessor con-
trol to conserve power, yet provide good smoke response. The system uses two filters
(one replaceable) that remove particulates while allowing smoke to pass.
Filter Supervision — Periodically, the filter system is tested for blockage using a
special thermal airflow sensor. In reasonably clean environments, the filter is ex-
pected to last at least as long as the smoke-entry test period required by NFPA 72. In
very dirty environments, the filter may need replacement more frequently.
Filter Trouble Reporting — If SS-F determines that filter blockage is imminent, a
warning trouble is indicated to the panel, followed by a return to normal. 72 hours after
this warning, the detector will disconnect, giving a continuous trouble signal.
Operation overview diagram:
Features
• Analog intelligent communications.
• High-performance filter removes
particulates down to 32 microns
(32-micron inner filter and replace-
able outer filter).
• Air delivery system is separately
powered and fully supervised.
• Outer filter is easily field replace-
able.
• Tolerant of external air velocity.
• Resistant to water vapor in
applications where occasional
non-direct water spray is per-
formed.
• Optional remote LED annunciator.
• Rotary DECADE address switches
with settings 01-99.
• Dual bi-color (red/green) LEDs
flash green when Normal and are
steady red in Alarm (systems with
SmartScan™ only).
• Compatible with the Gamewell
602, 610, 632, 654 and 658
FACPs.
• Requires auxiliary 24 VDC from
system or remote power supply.
Listings
Listings and approvals below
apply to the SS-F Filtrex Hostile
Area Smoke Head Analog Addres-
sable Detector with SmartScan™.
In some cases, the module may
not be listed by certain approval
agencies, or listing may be in
process. Consult factory for latest
listing status.
• UL Listed: file S1195.
• CSFM approved:
file 7272-1288:166.
• MEA approved:
file 230-01-E Vol. III.
SS-F CS-2473 09/01/06
6346cros.wmf
Page 1 of 2