SP200W Datasheet, PDF (1/2 Pages) Systemsensor advanced ideas. – Dual-Voltage Evacuation Speakers | |||
|
SpectrAlert® SP200 Series
Dual-Voltage Transformer Speakers
Description
System Sensorâs SP200
Series Speakers com-
bine performance, func-
tionality, and flexibility in
a line of dual-voltage
evacuation speakers.
Performance â With
its low total harmonic dis-
tortion, the SpectrAlert®
SP200 Series offers fi-
delity-quality sound out-
6710pho1.jpg
put. This provides
greater assurance that
the SP200âs output
closely matches its
source signal. This fidel-
ity sound quality is achieved at any of the SP200âs four field-selectable power
taps: 1/4, 1/2, 1, and 2 watts.
Functionality â Installation ease and functionality are achieved through
the SP200âs compact design, which allows flush-mounting to a 4" x 4" x 2-1/8"
(101.6 x 101.6 x 53.975 mm) backbox without an extension ring.
Flexibility â The SP200 is designed for a variety of application require-
ments. Offered with round and square grilles, the SP200 can be mounted to
either the wall or the ceiling. White and red grilles are available to meet
specific aesthetic requirements.
Features
⢠Fidelity sound quality.
⢠Low-profile design; fits standard
4" x 4" x 2-1/8" (101.6 x 101.6 x
53.975 mm) backbox without ex-
tension ring.
⢠Four field-selectable power taps:
easy to select and easy to
change (1/4 through 2 watts).
⢠Dual voltage settings: 25.0 and
70.7 volts.
⢠Ceiling- and wall-mount applica-
tions.
⢠Grilles available in white and red.
⢠Color-matched mounting screws.
Listings
Listings and approvals below
apply to the basic SpectAlert®
SP200 Series Dual-Voltage
Transformer Speakers. In some
cases, certain modules may not
be listed by certain approval
agencies, or listing may be in
process. Consult factory for
latest listing status.
⢠UL Listed: file S4048.
⢠CSFM approved:
file 7320-1209:186.
⢠MEA approved: file 353-98-E.
Engineerâs Specifications
Speaker shall be a System Sensor model ______ dual-voltage transformer
speaker capable of operating at 25.0 or 70.7 nominal VRMS. Speaker shall
be Listed to Underwriters Laboratories Standard 1480 for fire protective
signaling systems. Speaker shall have a frequency range of 400 to 4,000
Hz and shall have an operating temperature between 32°F and 120°F
(0°C and 49°C). Speaker shall have power taps which are selected by
shunts.