RSI-95
Description
Releasing Solenoid Interface
The Gamewell-FCI 600 Series analog addressable Fire
Alarm Control Panel (FACP) will provide all of the required
functions to control the releasing of bulk fire suppressant
materials. The Gamewell-FCI 600 Series analog address-
able FACPs are currently listed for NFPA 13 Sprinkler,
NFPA 15 Water Spray, NFPA 11 Low-Expansion Foam,
NFPA 16 Water Foam, NFPA 17 Dry Chemical, and NFPA
2001 Clean Agent types of suppressant. The Gamewell-
FCI Releasing Solenoid Interface (RSI-95) is an intelligent
addressable interface for the remote control and supervi-
sion of activation solenoids used in releasing applications.
The Releasing Solenoid Interface (RSI-95) is an address-
able Releasing Service Module, providing intelligent analog
addressable control functionality complete with full sole-
noid supervision and transient voltage suppression. Only
the RSI-95 can be used to actuate the releasing solenoid.
The RSI-95 is automatically bypassed during a Smart-
Start⢠or circuit initialization to prevent accidental dis-
charge during the generic configuration, should inputs be
inadvertently activated.
The analog addressable RSI-95 solenoid control module is
designed for use with any 600 Series FACP. To avoid
unplanned fire suppressant release, the RSI-95 assembly
is the ONLY assembly to be used to provide remote releas-
ing solenoid control. The circuit can control up to two amps
of DC power to the solenoid. The RSI-95 is powered and
controlled via the analog addressable signaling line circuit
and the solenoid power is obtained from the control panel
or a UL-Listed fire protection 24 VDC power supply. The
RSI-95 fully supervises the releasing solenoid.
RSI-95
Features
⢠Compatible with the Gamewell-FCI 600 Series analog
addressable fire alarm control panels.
⢠Provides full solenoid supervision.
⢠Transient voltage suppression.
⢠Mounts in its own unique base.
⢠Automatic bypass at system start-up.
⢠2.0 A of DC power for solenoid.
⢠Types of Suppressants:
â NFPA 13 Sprinkler.
â NFPA 15 Water Spray.
â NFPA 11 Low Expansion.
â NFPA 16 Water Foam.
â NFPA 17 Dry Chemical.
â NFPA 2001 Clean Agent.
NOTE: Releasing systems must be designed by
properly qualified personnel.
Installation Guideline
Install the RSI-95 according to NFPA 70, NEC 760, and
any applicable local codes.
NOTE: Only one each RSI-95 and solenoid may be con-
nected together for each releasing circuit. The RSI-95 is
designed to fit on a 4.688" (11.908 cm) by 2.125" (5.397
cm) deep electrical box (user supplied).
SmartStart⢠is a trademark of Honeywell International Inc.
An ISO 9000-2000 Company
SIGNALING
S521
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA ⢠Tel: (203) 484-7161 ⢠Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2007 Honeywell International Inc. All rights reserved.
www.gamewell-fci.com
CS-2046 Rev. A page 1 of 2
|
▷ |