English
Language : 

RPT-E3-UTP_13 Datasheet, PDF (1/1 Pages) Gamewell-FCI by Honeywell – Network Repeater
RPT-E3
Description
Network Repeater
The ARCNET Repeater Module (RPT-E3) is an optional
component of the E3 Series® and S3 Series fire alarm con-
trol panels. It allows the following remote E3 Series and S3
Series sub-assemblies to connect to the Broadband
network from remote locations:
• ILI-MB-E3/ILI95-E3 Series
• S3 Series, SLP (Smart Loop Panel-Main Board)
• ANX-SR/ANX-MR-UTP/ANX-MR-FO
• NGA
The RPT-E3 comes standard with network connections
using unshielded, twisted-pair, copper wire.The following
optional fiber-optic network connections using add-on
modules are available.
• FML-E3 multi-mode fiber module (optional)
• FSL-E3 single-mode fiber module (optional)
In addition, you can use the RPT-E3 to connect
remotely-mounted NGA modules to the network.
Installation
The RPT-E3 is adaptable for an installation in the standard
E3 Series and S3 Series cabinets. Typically, the RPT-E3
module is mounted on standoffs on the top of the right side
of the ILI-MB-E3/ILI95-MB-E3/ANX modules and SLP
motherboard.
For instructions on the installation of the RPT-E3, refer to
the following documents:
• E3 Series® UL Listing Document,
P/N: LS10080-051GF-E
• RPT-E3-UTP Installation Instructions, P/N: 9000-0580
• S3 Series UL Listing Document,P/N:LS10005-051GF-E
Specifications
Operating Voltage:
24 VDC FWR
Operating Current:
0.016 amp
Alarm Current:
0.017 amp
Operating Temperature: 32° to 120° F (0° to 49° C)
Relative Humidity:
0 to 93%, non-condensing at
90° F (32° C)
Wiring Specifications:
Copper Wire:
16 to 18 AWG twisted-pair,
unshielded
Up to 3,000 ft. (914.4 m) between
each node.
Fiber-Optic Cable:
(FML-E3 only)
Up to 200 microns optimized for
62.5/125 microns.
Up to 8 dB loss between nodes.
Fiber-Optic Cable:
(FSL-E3 only)
Optimized for 9/125 micrometer
cable @ 1310 nm.
Up to 30dB loss between nodes.
E3 Series®is a registered trademark of Honeywell International Inc.
UL® is a registered trademark of Underwriters Laboratories Inc.
Features
RPT-E3-UTP
• Listed under UL® Standard 864, 9th Edition.
• Provides the capability for networked E3 Series and
S3 Series sub-assemblies to connect in Styles 4 or 7
configurations.
• Offers standard unshielded, twisted-pair copper wire
network connections.
• Provides add-on fiber-optic modules that allow the net-
work connection through single or multi-mode fiber-optic
cables.
• Has 625K baud ARCNET Repeater.
• Uses the RPT-E3 to connect remotely-mounted NGA
modules to the network.
Ordering Information
Part Number Description
RPT-E3-UTP Network Repeater, unshielded, twisted-pair
FML-E3
FSL-E3
Multi-mode fiber-optic module for
RPT-E3-UTP (one channel)
Single-mode fiber-optic module for
RPT-E3-UTP (one channel)
SIGNALING
MEA
FM
Approved
City of
Chicago City of
APPROVED FDNY:
Approved Denver
S1869 3025415 COA #6077 7165-1703:0125 Class1 Approved
Class2
High Rise
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2016 by Honeywell International Inc. All rights reserved.
www.gamewell-fci.com
9020-0609 Rev. N page 1 of 1