English
Language : 

RCE-95 Datasheet, PDF (1/2 Pages) Gamewell-FCI by Honeywell – Relay control element device
RCE-95
Description
Relay Control Elements
The Gamewell-FCI Relay Control Element (RCE-95) is the
interface between the Gamewell-FCI 600 Series Fire
Alarm Control Panel (FACP) analog circuits and building
functions such as door holders, elevators, dampers,
motors and disconnects. The RCE-95 offers feedback
input points for positive confirmation of the controlled
device’s activity. The RCE-95 works with all 600 Series
analog addressable FACPs. For annunciation and feed-
back at the panel, Gamewell-FCI offers a Relay Control
Display (RCD). The RCD is only available with the IF632
and IF650 FACPs.
The RCE-95 is either surface or flush mounted and has an
integral LED which annunciates upon device activation.
Operation
The devices connect to the SLC circuit of the FACP via a
two-wire non- polarized circuit. In its quiescent mode, the
RCE-95 monitors its internal circuitry for status of the
device itself and supervises an external control circuit for
status.
When a status change is detected, the event can be pro-
grammed to display on the optional RCD module. When
an event is reported to the control panel that requires the
activation of the RCE-95, the control panel communicates
via the analog circuit to the RCE-95 for activation. The
integral LED is also lit for annunciation at the device.
Programming
The RCE-95 is programmed by setting a single DIP switch
easily accessible on the RCE-95’s printed circuit board.
The DIP switch is used to set the address of the device. All
other programming is accomplished at the Fire Alarm Con-
trol Panel, either through a laptop computer or the control
panel operator’s display.
Features
RCE-95
• Compatible with the Gamewell-FCI 600 Series analog
addressable FACPs.
• Form-C dry relay contacts.
• Event or manual controllable relay functions.
• Positive feedback of relay activation.
• LED annunciates activation.
• Fully supervised.
• Surface or flush mounting.
• Field programmable.
• Style 4, 6 , or 7 wiring.
• Screw terminals for field wiring connections.
An ISO 9000-2000 Company
SIGNALING
Microsoft® Windows® is a registered trademark of Microsoft® Corporation.
S521
FM
APPROVED 7300-1288:147
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2007 Honeywell International Inc. All rights reserved.
www.gamewell-fci.com
CS-2045 Rev. A page 1 of 2