English
Language : 

PM-9G Datasheet, PDF (1/1 Pages) Gamewell-FCI by Honeywell – PM-9G Power Supply and Battery Charger
PM-9G
Description
The Gamewell-FCI, PM-9G Power Supply is a 220/240
VAC, 50/60 Hz switching power supply. It provides power
to the Fire Alarm Control Panel, INCC Command Center,
INX Transponder assemblies, and all the E3 Series® com-
ponents. The PM-9G is a component of the following systems.
• E3 Series Expandable Emergency Evacuation System
• E3 Series Combined Fire Alarm and Mass Notification Systems
• E3 Series Broadband Voice Evacuation System
• NetSOLO® System
It includes 9 amperes of filtered and regulated 24 VDC
FWR. In addition, it has an internal battery charging circuit
that is capable of maintaining up to 55 A/H batteries.
Installation
Typically, the PM-9G Module can be mounted in the
following E3 Series cabinets:
• Cabinet B, Fire Alarm Control Panel
• Cabinet C, Command Center
• Cabinet C, Transponder
• Cabinet D, Command Center
• Cabinet D, Transponder
For information on the PM-9G installation, refer to the fol-
lowing documents:
- E3 Series Manual, P/N: LS10080-051GF-E
- PM-9G Installation Instructions, P/N: 9001-0055
- Mass Notification System Installation/Operation
Manual, P/N: LS10013-000GF-E.
Specifications
Input Voltage:
220/240 VAC @ 50/60 Hz
Input Current:
2.4 amps max.
Output Voltage: 24 VDC FWR
Output Current: 9 amperes Alarm max. continuous
Output Current: 5 amps max. continuous Standby
(when the PM-9G is used with the ILI-
E3 or the ILI95-E3 Series) (See Note 1)
Output Current: 4 amps max. continuous Standby
(when the PM-9G is used with any
AM-50 Series amplifier) (See Note 1)
Output Current: 1 amp battery charging current
Alarm Current: 0.050 amp
Operating
Temperature:
32° to 120° F (0° to 49° C)
Relative Humidity: 0 to 93% (non-condensing) at 90° F (32° C)
Dimensions:
27 W x 13 H x 5 D cm
(10 1/2” W x 5” H x 2” D)
Supervised and Non-Power-Limited
Note 1: Continuous standby loads in excess of .560 Amps
up to 5 Amps or 4 Amps may require a Generator Backup
or load shedding during an AC power failure.
E3 Series® and NetSOLO® are registered trademarks of Honeywell International Inc.
UL® is a registered trademark of Underwriters Laboratories Inc.
PM-9G Power Supply
and Battery Charger
PM-9G
Features
• Listed under UL® Standard 864, 9th Edition
• Listed under UL Standard UL2572 for Mass
Notification
• Includes 9 ampere, filtered, regulated power
supply
• Provides 1 ampere battery charging current
• Offers energy and space saving switching
technology
• Contains an integral battery charger capable of
recharging up to 55 A/H batteries
(Batteries not furnished)
Ordering Information
Part Number Description
PM-9G
Power supply and battery charger
29229
AC Line Filter Kit
SIGNALING
MEA
Approved
S1869 Vol. 14 FDNY: 7165-1703:0125
S1949 Vol. 19 COA #6077
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2015 by Honeywell International Inc. All rights reserved.
www.gamewell-fci.com
9021-60391 Rev. I page 1 of 1