NCM-1 Datasheet, PDF (1/1 Pages) Gamewell-FCI by Honeywell – Noise Control Module
NCM-1
Description
The Gamewell-FCI, NCM-1 Noise Control Module
(patented) is used to reduce the common noise (for
example, noise that is present on both conductors)
on the Signaling Line Circuit (SLC). The NCM-1
allows the use of untwisted, unshielded wire on the
SLC. Applications that have audio or fire fighters’
telephones require the use of twisted/shielded wiring
for all circuits including the SLC. The NCM-1 may
also be used in these applications to further reduce
the common mode noise.
Installation
To wire the NCM-1, connect it directly in line with the
SLC Loop. To connect the SLC circuit, the NCM-1
includes a pig-tail lead. To determine the maximum
wiring distance, refer to Table 1. All distances are
rated a maximum allowable distance and AWG wire.
Note: For systems without shield, cut the white wire.
Specifications
Table 1 lists the SLC wiring specifications that do not
include audio for the following Systems.
• E3 Series (Expandable Emergency Evacuation) System
• S3 Series (Small Addressable FACP) System
• 7100 Series System
Table 1: E3 Series®, S3 Series and 7100 Series
SLC Wiring Specifications (Without Audio)
More Than
Maximum
One Acceptable Distance
Conduit Shield Twisted-Pair SLC Loop? Wire AWG. Per Loop
NO NO
NO
YES
12-18 750 ft/Loop
NO
12-18
1,000 ft
NO NO
YES YES or NO 12-18 2,000 ft/Loop
NO YES
NO
YES or NO 12-18 2,000 ft/Loop
YES YES
NO
YES
12-18 2,000 ft/Loop
NO
12-14
5,000 ft
YES NO
YES
YES
12-18
3,000 ft
NO
12
10,000 ft1
YES NO
NO
YES
12-18 500 ft/Loop
NO
12-18
2,000 ft
NO YES YES
YES
12
10,000 ft1
NO
12
10,000 ft1
YES YES YES
YES
12
10,000 ft1
Note1: A smaller gauge wire will support shorter distances as follows:
• 14 AWG. 8,000 ft. Maximum
• 16 AWG. 4,875 ft. Maximum
• 18 AWG. 3,225 ft. Maximum
E3 Series® is a registered trademark of Honeywell International Inc.
Noise Control Module
Black
White
Red
SLC Loop “-“ (Black)
Shield (White)
SLC Loop “+” (Red
NCM-1
Features
• Mounts in a cabinet or external enclosure.
• Uses multiple NCMs for T-Tapped non-shielded
connections.
• Connects directly to the Signaling Line Circuit.
• Provides Pig-Tail Type connections.
• Patented Design (U.S. Patent # 5, 210, 523).
Ordering Information
Part Number Description
NCM-1
Noise Control Module
SIGNALING
MEA
Approved
FDNY:
CS68 COA #:289-91-E 7165-0028:0141 S2424
7165-0028:0153
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2013 by Honeywell International Inc. All rights reserved.
www.gamewell-fci.com
9021-60577 Rev. C page 1 of 1