MMI-6SF Datasheet, PDF (1/2 Pages) Gamewell-FCI by Honeywell – Multi-Mod 6 zone interface module
Description
The Velociti™ Series, multi-mod six zone interface
module (MMI-6SF) provides six (6), Style B (Class
B) or three (3), Style D (Class A) supervised initiat-
ing device circuits (IDC) suitable for use with
U. L. Listed conventional 2-wire smoke detectors
as well as any normally open contact device.
The VelocitiTM Series use a communication proto-
col that substantially increases the speed of com-
munication between the sensors and certain FCI
analog addressable fire alarm controls. These de-
vices operate in a grouped fashion. If one of the
devices in the group has a status change, the
panel’s microprocessor stops the group poll and
concentrates on the single device. The net effect is
response speed up to five times greater than ear-
lier designs.
The MMI-6SF connects to the signaling line circuits
(SLC) of the FCI analog addressable series fire
alarm control panels. Each of the MMI-6SF initiat-
ing device circuits occupies its own address on the
system’s SLC allowing each to be fully programma-
ble in its control-by-event sequence of operation.
The address of the first initiating device circuit is
set with a pair of rotary dials. Each remaining cir-
cuit is automatically assigned to its own subse-
quent address. The MMI-6SF module includes an
address disable jumper matrix to allow a maximum
of two unused addresses to be turned off to free
these addresses for other purposes. An additional
pair of jumpers selects either Style B or Style D
circuit configurations.
Each circuit has its own status LED that flashes to
indicate proper polling and lights steadily when the
output has been activated.
Velociti™ Series
MMI-6SF
Multi-Mod Six Zone
Interface Module
MMI-6SF
Features
• Each MMI-6SF module provides six (6), Style B
(Class B) or three (3), Style D (Class A) individually
addressable individually programmable initiating
device circuits.
• Suitable for use with U. L. Listed, compatible 2-wire
conventional smoke sensors and normally open
contact devices.
• Removable wiring terminal blocks allow ease of
installation and servicing terminal.
• Blocks can accommodate 12 to 18 AWG wire.
• Flexible jumper configuration feature allowing
one or two monitoring circuit addresses to be disabled.
• Individual LED indicators*.
• Ideal for retrofit applications.
• As many as thirty-six (36), initiating device circuits in
one 12” x 24” x 6.5” cabinet.
• Two (2), mounting cabinets available for two (2),
(MBB-2 cabinet) to six (6), (MBB-6 cabinet) units.
• Bicolor LEDs flash green whenever the sensor is
addressed, and light steady red on alarm.*
Note: *Only the red LED is operative in panels that do not oper-
ate in Velociti™ mode.
An ISO 9001-2000 Company
Velociti™ and E3 Series™ are trademarks of Fire Control Instruments.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2006 Gamewell-FCI. All rights reserved.
www.gamewell.fci.com
9020-0633 Rev. B page 1 of 2