English
Language : 

INX Datasheet, PDF (1/4 Pages) Gamewell-FCI by Honeywell – Intelligent Network Transponder
INX
Description
The Gamewell-FCI, INX Intelligent Network Transponder
serves as the point of distribution for the system’s audio
and fire fighter telephone risers. It is a component of the
following systems.
• E3 Series® Expandable Emergency Evacuation System
• E3 Series Combined Fire and Mass Notification System
• E3 Series Broadband Audio Evacuation System
The INX occupies a single node on the E3 Broadband net-
work and is connected by a single pair of unshielded,
twisted wires, fiber-optic cable or any combination of the
two. Each E3 Broadband node can be spaced on the net-
work up to a maximum distance of 3,000 feet (914.4 m) or up
to an 8 dB loss using a fiber-optic cable. Built-in isolation at
each node permits Style 4, Style 6, and Style 7 network
configurations.
The E3 Broadband Audio Evacuation System is a peer-to-
peer, self-regenerating, token ring network comprised of up
to 64 individual nodes. In addition, the Addressable Node
Expander (ANX) board expands the network to 122 nodes.
The E3 Broadband employs proven technology and
extends it to accomplish emergency voice evacuation, 2-
way fire fighter communications, and building control appli-
cations. It is unique in the industry since it requires only a
single pair of wires or fiber-optic cable connections
between nodes to convey all fire alarm, digital voice, fire
fighter communications, paging, and building control sig-
nals. This system provides a 16 message capacity with up
to a 3 minute duration per INX. Messages are easily field-
configurable with a laptop computer
A typical INX assembly consists of the following:
• an Intelligent Network Interface-Voice Gateway
(INI-VGX) module
• a PM-9/PM-9G power supply
• up to 4 AM-50 Series amplifiers including a minimum of
one backup amplifier
It is enclosed in a compact 19” enclosure capable of
accommodating up to 12 A/H size batteries. The modular
approach of the E3 Broadband greatly simplifies the design
and the installation and allows the complete flexibility in ret-
rofit or add-on situations. This system is ideal for a wide
range of complex system applications including high-rise or
campus installations.
E3 Series® is a registered trademark of Honeywell International Inc.
UL® is a registered trademark of Underwriters Laboratories Inc.
Intelligent Network Transponder
INX
Features
• IBC Seismic Certified
• Listed under UL® Standard 864, 9th Edition.
• Listed under UL Standard UL2572 for Mass Notification.
• Offers all communication signals and control-by-event
sequences over two wires or fiber-optic cable including:
audio evacuation, voice paging, fire fighter intercom,
and building control signals.
• Integrates with INCC command centers and additional
INX transponders to create a complete audio
evacuation system with up to 122 nodes.
• Distributed architecture, including Style 7 wiring config-
urations, allow system components to continue normal
operation with NO loss of function during single line
fault conditions.
• Uses state-of-the-art digital signal processor (DSP)
technology for efficient audio compression and filtering.
• Software-programmable multi-channel digital audio
applications.
• One Style 4 signaling line circuit (SLC) supporting up to
32 addressable speaker circuits (AOM-2SF used for sin-
gle channel circuits and 16 addressable phones circuits
AOM-TELF).
• Up to 150 watts of audio power provided by the AM-50
Series amplifiers with an 50 watts of standby amplifier
enclosed in a single, compact wall-mounted cabinet.
• Each AM-50 Series amplifier provides two individually
activated speaker circuits supplying 50 watts total.
SIGNALING
FM
APPROVED
MEA
Approved
FDNY:
City of
Chicago
Approved
City of
DENVER Reference
Certificate
S1869 3017416 COA #-217-03-E 7165-1703:0125 - Class 1 Approved
7170-1703:0126
-
-
Class 2
High Rise
of Compliance
VMA-45894-02C
(Revision 1)
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2013 by Honeywell International Inc. All rights reserved.
www.gamewell-fci.com
9020-0541 Rev. M page 1 of 4