English
Language : 

INI-VGC_13 Datasheet, PDF (1/4 Pages) Gamewell-FCI by Honeywell – Intelligent Network Command Center
INCC and
E3 LOC, INCC CAB-B
Description
The Gamewell-FCI, INCC Intelligent Network Command
Center serves as the point of interface between an opera-
tor and the system’s audio evacuation, fire fighter inter-
com, and building control circuits. It is a component of the
following systems.
• E3 Series® Expandable Emergency Evacuation
• E3 Series Combined Fire and Mass Notification System
• E3 Series Broadband Audio Evacuation System
• NetSOLO® System
The INCC occupies a single node along the E3 Broadband
network and is connected by a single pair of twisted,
unshielded wire, fiber-optic cable or any combination of
the two. Each E3 Broadband node can be spaced along
the network at a maximum distance of 3,000 feet (914.4 m)
or up to an 8dB loss using fiber-optic cable. Built-in isola-
tion at each node permits Style 4, Style 6, and Style 7 net-
work configurations.
The E3 Series Broadband Audio Evacuation System is a
peer-to-peer, self-regenerating, token ring network com-
prised of up to 64 individual nodes. in addition, the
Addressable Node Expander (ANX) board expands the
network to 122 nodes. The E3 Broadband employs proven
technology and extends it to accomplish emergency voice
evacuation, 2-way fire fighter communications, and build-
ing control applications. It is unique in the industry
because it requires only a single pair of wires or a fiber-
optic cable connection between nodes to convey all fire
alarm, digital voice, fire fighter communications, paging,
and building control signals.
The typical INCC and E3 LOC, INCC-CAB-B sub-assem-
blies consist of the following:
• an Intelligent Network Interface-Voice Gateway
(INI-VGC) Module
• one or more Addressable Switch Modules (ASM-16)
• one Network Graphic Touchscreen Annunciator (NGA)
The INCC Command Center’s INI-VGC module also pro-
vides connections for an optional emergency Voice Page
Microphone as well as a Fire Fighter Telephone Handset.
The INI-VGC is a fully digital voice/tone generator using
state-of-the-art Digital Signal Processing (DSP) technol-
ogy to produce the clearest, most audible signal possible.
The INI-VGC provides an output to a local speaker for
message verification and testing. It is ideal for a wide
range of complex System Applications including high-rise
or campus installations.
Intelligent Network Command Center
INCC
Features
• Listed under UL® Standard 864, 9th Edition.
• Listed under UL Standard UL2572 for Mass Notification.
• All communication signals and control-by-event
sequences over twisted, unshielded pair of wires or
fiber-optic cable including:
- Audio Evacuation - Fan Control & Damper
Shutdown
- Voice Paging
- Door Closures
- Fire Fighter Intercom - Fire Alarm and Control Devices
- Elevator Control
- Horn/Strove Circuit Activation
• Distributed architecture, including Style 7 wiring config-
urations, allow system components to continue normal
operation with NO loss of function during single line
fault conditions.
• Integrates with INX transponders and additional INCC
command centers to create a complete audio evacua-
tion system with up to 122 nodes.
• Each INI-VGC supports up to 16 ASM-16 switch mod-
ules for a total of 256 switches.
• INI-VGC connects to a Voice Page Microphone and
Fire Fighter’s Handset.
• Redundant Command Centers with Microphone and
Fire Fighter’s Handset can be easily configured by
adding additional INCCs.
• Advance Boolean logic-based programming such as
AND, OR, NOT, NOR, time delay, and calendar func-
tions configurable through computer programming.
• Advanced digital signal processor (DSP) technology for
efficient audio compression and filtering. Uses network
data transfer rate at 625K baud.
SIGNALING
MEA
FM Approved
APPROVED
FDNY
City of
Chicago
Approved
S1869 3025415 COA # 6077 7165-1703:0125 Class 1
Class 2
High Rise
City of
Denver
Approved
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2013 by Honeywell International Inc. All rights reserved.
www.gamewell-fci.com
9020-0542 Rev. J page 1 of 4