English
Language : 

ILI-MB-E3 Datasheet, PDF (1/2 Pages) Gamewell-FCI by Honeywell – Intelligent Loop Interface-Main Board
ILI-MB-E3
Series
Description
ILI-MB-E3
The Intelligent Loop Interface-Main Board (ILI-MB-E3) is
the main interface for the E3 Series® product line. With its
state-of-the-art 32 bit RISC processor, this compact “panel
on a board” provides a powerful addition to Gamewell-
FCI’s single pair conductor solutions. This intuitive design
provides two (2), signaling line circuits, two (2), notification
application circuits, local energy city box output, auxiliary
relay functions, and auxiliary power output. These features,
combined with built-in network and serial protocols, allow
this module to support a host of new and existing products,
resulting in a building block approach to fire alarm panel
design.
The ILI-MB-E3 is network ready and occupies one of 64
nodes, operating at 625K baud. When this sub-assembly is
integrated with proven Broadband components, the result
is a flexible yet powerful integrated audio solution. When
transmitting to remote locations, the optional RPT-E3 pro-
vides the ILI-MB-E3 with valuable signal boosting and tran-
sient protection, as well as connectivity using both wire and
fiber-optic cables.
The ILI-MB-E3 provides two (2), signaling line circuits and
terminals for the connections to up to 159 detectors and
159 modules per SLC in Velociti®. In clip mode, each SLC
supports 99 detectors and 98 modules. The RS-485 inter-
face can support up to a total of sixteen (16), ASM-16 and/
or sixteen (16), ANU-48 remote LED driver modules.
The ILI-MB-E3 relay outputs include system alarm, super-
visory, and system trouble contacts. The ILI-MB-E3 pro-
vides output for a local energy city master box or remote
location which is non power-limited. All other wiring is
power-limited.
Intelligent Loop
Interface-Main Board
Features
ILI-MB-E3
ILI-MB-E3 and ILI-S-E3:
• Listed under UL Standard 864, 9th Edition
• Network ready integral 625K baud ARCNET
• 115.2K baud RS-232
• Signaling line circuits with:
- Two (2), Class A, Style 6, 7* or Class B, Style 4
circuits
- 40 Character user-defined text per device
- Capacity of 159 sensors and 159 addressable
modules per circuit
• 4100 event history log
*Style 7 wiring requires the use of System Sensor M500X
Isolator Modules.
ILI-MB-E3 Only:
• Two (2), notification appliance circuits, Class “A”, Style Z
or Class B, Style Y rated at 2.0 amps. per circuit
• RS-485 supporting sixteen (16), ASM-16 switch mod-
ules and/or ANU-48 LED driver modules
• Alarm, trouble, and supervisory dry contacts Form “C”,
rated at 2 amp. @ 30 VDC (resistive)
• Supports six (6), local/remote LCD-E3 annunciators and
five (5), LCD-7100 annunciators
An ISO 9000-2000 Company
SIGNALING
E3 Series,® NetSOLO,® and Velociti® are registered trademarks of Honeywell International
Inc.
S1869
FM MEA
City of
Chicago City of
APPROVED Approved
Approved Denver
3025415 231-06-E 7165-0694:268
Class 1
Class 2
Approved
7165-0694:269 High Rise
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2007 by Honeywell International Inc. All rights reserved.
www.gamewell-fci.com
9020-0605 Rev. e1 page 1 of 2