English
Language : 

GV-MP16-RC Datasheet, PDF (1/2 Pages) Gamewell-FCI by Honeywell – Fire Command Center Multiplexed Voice Multiplexed Voice
Description
The Gamewell Voice (GV) Multiplexed Evacuation System
Fire Command Center operates in conjunction with the 600
Series Fire Alarm Control Panel (FACP) in a building to pro-
vide automatic response to life safety emergencies.
The Gamewell Voice Master Panel Fire Command Center
includes all necessary features to provide an effective Voice
Evacuation and Fire Alarm Control system. The Gamewell
Voice Panel can be easily custom configured to satisfy the
needs of any configured Voice System application.The
Gamewell Voice Fire Command Center comes complete with
the Gamewell RS-484 Intelligent Interface Software for com-
munication to the Gamewell FACP. All Fire Alarm and Voice
Communication control are combined in a visually appeal-
ing single panel configuration.
Fire Department authorities easily take command of
evacuation, relocation procedures and emergencies from a
single Fire Command Center. Building management and Fire
Brigades easily monitor and control emergency responses
even before the professionals arrive.
The GV system includes capacity for 6 channel digital au-
dio. This provides for evacuation, stay-in-place, or other pub-
lic address announcements and automatic messages, and
fire fighter phones.
Fire Fighter Phones or Warden Stations may be included
as required. Smoke control, stair pressurization, and HVAC
shutdown can be completely automatic, unless controlled
manually by management or fire authorities, utilizing the as-
sociated Gamewell FACP.
System Configuration
Basic System includes:
Master Panel (GV-MPXX-RC, GV-MPXXP-RC)
Master Microphone Control
Remote Fire Annunciation and Control
Switch Control points
Dual Channel Digital Message Repeator
High Speed RS-485 communication loop
Optional
Integrated Master Fire Phone
600 Series
Fire Command Center
Multiplexed Voice
Evacuation System
Approvals
UL Listed, MEA Approved
Features
• True Multiplex 6 Channel Distributed Audio
• Complete Fire Alarm Control Functions
• Integrated Fire Phone, paging and manual EVAC
• Modular System - components added as needed
• Integrated 2 Channel Digital Message Repeater
• Live Microphone Page to any zone
• Fully Supervised
• Natural Sound Voice Recordings
• Built-in Alarm and Alert Signals
• Up to 4 minute message capacity
• All Voice control and audio data on single high speed
communications loop
• 3 minute message restart on microphone key
• 1000 Monitor & Control Points
CS-2176 09/01/06
Page 1