FC-2224 Datasheet, PDF (1/2 Pages) Gamewell-FCI by Honeywell – TWO-ZONE PANEL
DESCRIPTION
The FC-2224 Fire Alarm Control panel is a proven, versa-
tile, two-zone control with space to accommodate an op-
tional digital communicator. It meets the requirements of
NFPA Standard 72 for Central Station, Protected Premises,
and Remote (DACT) Supervising Station Fire Alarm Sys-
tems. It is Listed to UL Standard 864, inherently power lim-
ited and meets all UL transient immunity requirements.
The many features of the FC-2224 control provide a cost
effective approach to systems design, and allow a great de-
gree of flexibility in one enclosure. These features include
two (2) Class B, Style B initiating circuits and two (2) Class
B, Style Y notification appliance circuits, rated at 1.25 amps
each. Notification appliance circuits can be configured as
silenceable or non-silenceable.
DIP switch programming is used throughout, eliminating
the need for computers and associated software.
A time delay of 30, 60, or 90 seconds is available for
waterflow switches.
The control is housed in a red steel enclosure with a win-
dow offering a view of LEDs displaying the status of vital
functions. The surface mounted enclosure, with its slim ap-
pearance (3 3/8-inch depth) is designed to blend with any en-
vironment. Space is available for two (2) B-7R batteries.
Supervision of vital components, plug-in modules, func-
tional switches and standby batteries is provided.
The optional digital communicator includes a wide range
of selectable transmission formats to communicate to most
central stations. Other features of the communicator are: A
line-active indicator for each of two phone lines, “Kiss-Off”
signal LED, dual “low telephone voltage detect” circuitry
and programmable event codes per format. The FC-2224 is
programmable for AC power loss delay required for DACT
operation.
An optional serial annunciator driver allows remote alarm
annunciation to as many as four (4) Model FC-2866 remote
annunciators.
Other optional modules include the FC-2880 I/O module
which provides 34 pre-defined open collector outputs that
can be used to drive LEDs or relays.
FC-2224
TWO-ZONE PANEL
CONVENTIONAL FIRE ALARM CONTROL
FEATURES
· Inherently Power Limited
· DIP Switch Programming
· Choice of Output Patterns Including
ANSI S3.41
· Programmable Time Delay for
Waterflow Switches
· Periodic Trouble Reminder
· Walk Test Feature
· Optional Digital Communicator with
Multiple Reporting Formats
· Serial Annunciator Output (Optional)
· Surface Mount Technology
AGENCY APPROVALS
UL
CSFM
S1869
Approved
Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed by Fire Control In-
struments, Inc. for their use. Specifications subject to change without notice.