English
Language : 

ET70-R Datasheet, PDF (1/4 Pages) Gamewell-FCI by Honeywell – Wheelock
Building Intelligent N etw orks
www.firecontrolinstruments.com
GENERAL
FEATURES
Wheelock has enhanced the ET Series • DesignedtomeetorexceedNFPA/ANSI
high-performance Speakers and Speaker
Standard and ADA Accessibility Guide-
Strobe combinations. These speakers are
lines. Meets OSHA 29 Part 1910.165.
specifically designed to meet the critical
needs of the life safety industry for voice
and tone signaling. These dual voltage (25/
70 volt), multiple tap (from 1/8 to 8 watts)
audio systems now incorporate a new
low-profile design which results in more
space in standard electrical backboxes.
ET Series Speakers and Speaker Strobes
now incorporate a new speaker mounting
plate for faster and easier installation with
a built-in level adjustment feature, and a
new aesthetically pleasing two-screw grille
cover. Additionally, the ET Series Speaker
Strobe models now incorporate the
new low-current, reduced-inrush,
Wheelock RSS Series Non-Sync/Sync
Strobes (synchronization of the strobe
flash is achieved when used with the
Wheelock SM or DSM Sync Module).
ET Series Speaker Strobes are designed
with maximum performance, reliability and
cost-effectiveness while meeting or ex-
ceeding the latest requirements of NFPA
72 (National Fire Alarm Code), ANSI 117.1
(American National Standard of Accessible
and Usable Buildings and Facilities), and
UL Standard 1971(Standard for Signaling
Devices for the Hearing Impaired). ET
Speaker Strobes, when properly specified
and installed in accordance with NFPA/
ANSI standards, can provide the equiva-
lent facilitation allowed under ADA Acces-
sibility Guidelines (ADAAG General Sec-
tion 2.2) by meeting or exceeding the il-
lumination which results from the ADA
specified strobe intensity of 75 candela at
50 feet (15.24 m). This is an illumination
of 0.030 lumens per square foot.
ET Series Speaker Strobes are UL listed
for indoor use, ceiling- and wall-mounting,
under Standard 1971 for Signaling Devices
for the Hearing Impaired and Standard 1480
• High-efficiency speakers designed for
maximum output at minimum wattage
across 400 to 4,000 Hz frequency range.
• Field-selectable taps for 25 or 70 VRMS
operation from 1/8 watt up to 8 watts in
3-dB steps.
• Sealed-back speaker construction
for extra protection and improved
audibility.
• Easy installation with In/Out screw
terminals using #12 AWG (3.25 mm²)
to #18 AWG (0.75 mm²) wiring.
• ET Series Speaker Strobe models are
available with the new RSS Series Non-
Sync/Sync Strobes in 15, 15/75, 30, 75,
and 110 candela for wall mounting; and
30, 75, and 100 candela for ceiling mount-
ing. When used in conjunction with
the Wheelock SM or DSM Sync Mod-
ules, these non-sync/sync strobes pro-
duce a synchronized strobe flash for
compliance with ADA guidelines con-
cerning photosensitive epilepsy.
• The 15/75 candela wall-mounted
strobes are listed at 15 candela under
UL standard 1971 and meet 75 candela
intensity on axis for ADA guidelines,
with low current draw.
• All strobe inputs compatible with stan-
dard reverse-polarity-type supervision of
circuit wiring by an alarm panel.
• The new speaker mounting plate
provides faster, easier installation in
attractive package styles for flush, semi-
flush, or surface mounting to standard
low-cost backboxes. Special slots are
provided for ease in leveling speaker and
speaker-strobe models.
• ET-1010 or ET-1080 Series models
available for vandal-resistant die-cast
speakers and speaker strobes.
for Speaker Appliances. They use a Xenon
flashtube with solid state circuitry enclosed
in a rugged LEXAN® lens to provide
. maximum reliability for effective visual
signaling.
LEXAN® is a registered trademark of GE Plastics, a subsidiary
of General Electric Company.
Wheelock
ET Series
ET70 SERIES
ET90 SERIES
ET90 Series
Speaker Strobe
ET70 Series
Speaker Strobe
S2652 (Speakers)
S2652/S5391
(Strobe/Speakers)
151-92-E
Vol. XXI
California
State Fire
Marshal
7135-0785:134
7125-0785:146
An ISO 9001 Company
Specifications are provided for information only, and are
not intended to be used for installation purposes and are
believed to be accurate. However, no responsibility is
assumed by Fire Control Instruments for their use.
Specifications subject to change without notice.
© 2003
All Rights Reserved
9020-0579/Ver. 1.0
Page 1 of 4
A Honeywell Company