English
Language : 

DRBC-1 Datasheet, PDF (1/1 Pages) Gamewell-FCI by Honeywell – DUAL RATE BATTERY CHARGER
DRBC-1
DUAL RATE BATTERY CHARGER
DESCRIPTION
The DRBC-1 Dual Rate Battery Charger is a solid-state,
fully automatic device that will provide sufficient current to
maintain compatible rechargeable batteries at full charge re-
gardless of variations in line voltage or load.
Two charging modes are provided: FLOAT, which main-
tains a charged battery in fully charged condition and HIGH
RATE, which permits a discharged battery to be charged rap-
idly. The charger senses the battery condition by monitoring
the current drawn by the battery at a particular cell voltage. If
the battery attempts to draw more than a specified amount of
current from the charger, it will automatically switch to the
High Rate mode and maintain a high rate of charge current
until the batteries requirements are met. The DRBC-1 will
then automatically switch to the Float mode.
The DRBC-1 may provide system compatible battery su-
pervision, high rate indication and self-contained trouble in-
dications with audible trouble silence (with “ring-back”).
Over-current and reverse polarity protection are provided as
well as internal fuse protection.
The charger is enclosed in a louvered 16 gauge steel enclo-
sure 12" W x 13" H x 4" D (30.48 x 33.02 x 10.16 cm) with a
viewing window to readily show all status indicators without
opening the cabinet.
AGENCY APPROVALS
UL (Std 864)
S2464
C.S.F.M.
7300-0694:103
FEATURES
· Two Charging Modes
· Self-contained
· Trouble Sounder with “Ringback”
Silence Switch
· Output for FCI Model RTI Remote
Trouble Indicator
· Battery Supervision
· Fully Automatic
· Solid State Design
· D.C. Voltage Regulation
· Electronic Current Limiting
SPECIFICATIONS
Input voltage
120 VAC +10%, -15%, 60 Hz
Input current
2.5 amperes max.
Output voltage
24 VDC nominal*
Output current
5 amperes nominal
Charge rate
4.5 ampere hours per hour (dependent upon battery state of charge)
Voltage stability
Operating temperature
± 1% with line variation
32o F to 120o F (0o C to 49o C)
Operating humidity
85%
Functional switches
“HIGH-RATE”
“TROUBLE SILENCE”
Indicators
“AC ”
Green LED
“TROUBLE”
Yellow LED and audible trouble sounder.
“HIGH RATE”
Red LED
DC Ammeter
Indicates battery charging current
DC Voltmeter
Indicates battery terminal voltage
NOTE: *The nominal output voltage can be adjusted internally to accommodate any common 24 VDC battery type.
Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed
by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice.
© 1997 All Rights Reserved
16 Southwest Park, Westwood, MA 02090 USA TEL: (781) 471-3000 FAX: (781) 471-3099
An ISO 9001 Certified Company
9020-0054/Ver. 1.4