English
Language : 

B210LP Datasheet, PDF (1/2 Pages) Systemsensor advanced ideas. – Low-Profile Intelligent Combination Smoke Detector
Velociti® Series
ABD-2F and ABD-RT2F
Description
The Gamewell-FCI Velociti® Series, ABD-2F and address-
able projected beam smoke sensor is uniquely suited to
sense smoke in hostile environments or open areas with
high ceilings where spot-type sensors are unsuitable or
difficult to install and maintain. It is intended for use in the
signaling line circuits with the following sub-assemblies.
• E3 Series®, ILI-MB-E3 and ILI-S-E3 (Velociti mode only)
• S3 Series, SLC-PM (Signaling Line Circuit-Personality
Module)
The ABD-2F consists of a combination transmitter/
receiver unit and a reflector. When smoke enters the path
between the unit and the reflector, it causes a reduction in
the signal, and when the smoke level reaches the prede-
termined threshold, an alarm results.
A unique single-ended reflective design offers simpler
installation than the traditional transmitter and receiver
types of beam sensors. Alignment is swiftly accomplished
via an optical sight and a 2-digit signal strength meter inte-
gral with the product. Listed for operation from –22° F to
131° F, the ABD-2F can be installed in garages, ware-
houses and other hostile environments where temperature
extremes exceed the capability of spot-type sensors.
The Velociti® Series uses a communication protocol that
substantially increases the speed of communication
between the sensors and Gamewell-FCI analog address-
able fire alarm controls. These devices operate in a
grouped fashion. If one of the devices in the group
changes status, the panel’s microprocessor stops the
group poll and concentrates on the single device. The net
effect is response speed up to five times greater than ear-
lier designs.
The unit has four standard sensitivity selections along with
two Acclimate settings. When either of the two Acclimate
settings are selected, the sensor will automatically adjust
its sensitivity using the advanced software algorithms to
select the optimum sensitivity for the specific environment.
Velociti® and E3 Series® are registered trademarks of Honeywell International Inc.
Single-Ended Reflected Type
Beam Smoke Sensor
Features
ABD-2F/RT2F
• Includes a single-ended, reflective design.
• Has six user-selectable sensitivity levels.
• Spans a 16 to 328 foot (4.9 to 99.9 m) detection range.
• Compatible with the E3 Series® ILI-MB-E3 and ILI-S-E3
or the S3 Series, SLC-PM.
• Contains an integral sensitivity test feature (ABD-2SF).
• Designed with a digital display - no special tools
required.
• Provides a user-friendly alignment procedure.
• Offers an integral automatic gain control that compen-
sates for signal deterioration from dust build-up.
• Available with an optional Remote test station.
SIGNALING
S1913
FM
MEA
Approved
APPROVED
FDNY
3023594 COA #:219-02-E 7260-1703:0120
Vol. VI
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2013 by Honeywell International Inc. All rights reserved.
www.gamewell-fci.com
9020-0623 Rev. F page 1 of 2