English
Language : 

AMM-2IF Datasheet, PDF (1/1 Pages) Gamewell-FCI by Honeywell – Monitor module, two circuit, Style B, Class B
Velociti® Series
AMM-2IF
Description
Addressable Dual Monitor Module
The Gamewell-FCI Velociti® Series, addressable dual
monitor module, AMM-2IF, features two (2), Style B, Class
B initiating device circuits, each with an end-of-line resistor.
This module provides addresses for any device or group of
devices connected to each circuit. Any alarm initiating
devices with normally open (N.O.) dry contacts, such as
heat detectors, 4-wire projected beam smoke detectors, 4-
wire smoke detectors, water flow switches, tamper
switches, manual stations, etc. may be installed in these
circuits.
The Velociti® Series use a communication protocol that
substantially increases the speed of communication
between the sensors and certain Gamewell-FCI analog
addressable fire alarm controls. These devices operate in a
grouped fashion. If one of the devices in the group has a
status change, the panel’s microprocessor stops the group
poll and concentrates on the single device. The net effect is
response speed up to five times greater than earlier
designs.
The first circuit address is set via a rotary switch. The sec-
ond circuit is automatically assigned the next higher
address. The module has a single panel-controlled red
LED.
The AMM-2IF module is designed for installation in the sig-
naling line circuit of any Gamewell-FCI addressable control
panel. The AMM-2IF is designed to mount in a 4” square
junction box, 2 1/8” deep. The initiating device circuit of the
AMM-2IF can support a maximum line resistance of up to
40 ohms allowing the use of linear heat detection devices.
Ordering Information
Model Description
AMM-2IF Monitor module, two circuit, Style B, Class B
Features
AMM -2IF
• Compact size allows easy installation
• Class B, Style B, initiating device circuits
• Visual rotary, decimal switch addressing (01-159)
• 40 ohm line resistance for each initiating circuit
• Accommodates any normally open contact device
• Bicolor LEDs flash green whenever the module is
addressed, and light steady red on alarm*
*Note: Only the red LED is operative in panels that do not operate
in Velociti® mode.
Specifications
Supervisory current: 0.0075 amp.
Alarm current:
.0057 amp. (LED lit)
Operating temperature: 32° to 120° F (0° to 49° C)
Relative humidity:
10 to 93% (non-condensing)
Dimensions:
4 1/2” H x 4” W x 1 1/4” D
(11 H x 10.2 W x 3 D cm) (Mounts in a 4”
square by 2 1/8” deep box).
End-of-line resistor: 47 K ohms
An ISO 9001-2000 Company
SIGNA LIN G
Velociti® and E3 Series® are registered trademarks of Honeywell
International Inc.
S1949
FM MEA
APPROVED Approved
3023594 227-03-E Vol.IV 07300-0694:232
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2008 Honeywell International Inc. All rights reserved.
www.gamewell-fci.com
9020-0629 Rev. D1 page 1 of 1