English
Language : 

5601 Datasheet, PDF (1/1 Pages) Gamewell-FCI by Honeywell – MECHANICAL HEAT DETECTORS
SYSTEM SENSOR
5600 SERIES
MECHANICAL HEAT DETECTORS
The System Sensor 5600 Series mechanical heat detectors
offer a low cost means for property protection against fire,
and for non- life safety installations where smoke detectors
are inappropriate.
The 5600 Series offers both single and dual circuit models,
each available with low or high temperature ratings, and
fixed temperature or rate of rise activation. The rate of rise el-
ement is restorable to accommodate field testing of the unit.
The detectors mount readily on single gang or octagonal
back boxes. They can also mount on a four inch square box
with aid of a square to round plaster ring. The mounting
bracket is reversible to allow for flush and surface mount in-
stallations.
The 5600 units provide clear markings readily visible on
the unit to ensure the proper application. Alphanumeric char-
acters identify the type of detector and temperature rating,
both in Fahrenheit and Celsius. Fixed temperature models
are identified “FX” while combination units are marked
“FX/ROR”. The detector also features positive indication of
actuation of the fixed temperature portion. The collector disc
drops from the unit making it readily identifiable.
Electrical Specifications
Operating Voltage
Contact Ratings
6 -125 VAC
3A
6-28 VDC
1A
125 VDC
0.3A
FEATURES
• Attractive Low Silhouette design
• Multiple Configurations Available
• Single and Dual Circuit Models
• Fixed Temperature and Combination
Fixed Temperature/Rate-Of-Rise
• Readily Visible Alphanumeric
Markings
• Standard 3.5 or 4-inch Octagonal
Mounting
• Single Gang or Standard 4” Square
Mounting with Plaster Ring
S2101
3016008
199-33-E
7270-1209:227
RATINGS AND ORDERING INFORMATION
Model
Circuit Temp. Rating
Type
Max. UL Spacing - 10 Foot Ceiling*
5601
Single 135o F (57o C)
FT + ROR
50 ft. x 50 ft. (15.24 m x 15.2 m)
5602
Single 194oF (90oC)
FT + ROR
50 ft. x 50 ft. (15.24 m x 15.2 m)
5603
Single 135o F (57o C)
FT only
25 ft. x 25ft. (7.62 m x 7.62 m)
5604
Single 194oF (90oC)
FT only
25 ft. x 25ft. (7.62 m x 7.62 m)
5621
Dual 135o F (57o C)
FT + ROR
50 ft. x 50 ft. (15.24 m x 15.2 m)
5622
Dual 194oF (90oC)
FT + ROR
50 ft. x 50 ft. (15.24 m x 15.2 m)
5623
Dual 135o F (57o C)
FT only
25 ft. x 25ft. (7.62 m x 7.62 m)
5624
Dual 194oF (90oC)
FT only
25 ft. x 25ft. (7.62 m x 7.62 m)
* Refer to NFPA 72 for guidelines for spacing reductions when ceiling heights exceed 10 feet.
Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed by Gamewell-FCI
for their use. Specifications subject to change without notice.
© 2006 All Rights Reserved
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118
www.gamewell-fci.com
An ISO 9001 Certified Company
9020-0590 Rev. B