AM-50 Series
Description
The Gamewell-FCI, AM-50 Series amplifiers are a 50 watt,
digital, switching power amplifier. The following lists the 2
types of AM-50 Series amplifiers that may be ordered.
• The AM-50-25 amplifier produces 25 VRMS audio output.
• The AM-50-70 amplifier produces 70.7VRMS audio output.
The amplifiers are components of the following E3 Series®
Systems.
• E3 Series Expandable Emergency Evacuation System
• E3 Series Combined Fire and Mass Notification System
• E3 Series Broadband Voice Evacuation System
WARNING: AM-50 Series Amplifiers Node Restriction:
The INI-VGX can support up to 4 AM-50 Series amplifiers
with the same output voltage. However, you cannot wire an
AM-50-25 amplifier and an AM-50-70 amplifier to the same
INI-VGX Voice Gateway Node.
Each AM-50 Series amplifier provides 2 speaker circuits
that can be wired Style Y (Class “B”) or Style Z (Class “A”).
The terminal connections can accommodate up to 12
AWG, twisted-pair, shielded wire. Both speaker circuits pro-
duce a combined total of 50 watts of power. The 50 watts
of power can be divided between the 2 integral Class A/B
speaker circuits. The 2 speaker circuits may be individually
activated and supervised by an INI-VGX Transponder
Voice Gateway.
The AM-50 Series amplifier can be programmed to broad-
cast 16 messages generated from its local INI-VGX Voice
Gateway. In addition, the AM-50 Series amplifiers produce
superior clarity for intelligible LIVE voice paging.
When the selected System Sensor, SpectrAlert® Advance
Series speakers are used with the Manufacturer’s 520 Hz
audiophile, the E3 Series® System is compliant with UL
Standard 464 Low Frequency requirements.
For additional information, refer to the SpectrAlert Advance
Series Data Sheet, P/N:9021-60346.
Installation
As many as four AM-50 Series amplifiers can be installed
in the following cabinets when supervised and controlled
by an INI-VGX Voice Gateway.
• Cabinet B, INX CAB-B
• Cabinet C, INX-CAB-C
• Cabinet D, INX-CAB-D
EU3L®Seirsieas®regaisntderSepdetcratrdAelemrat®rk
are registered trademarks of Honeywell
of Underwriters Laboratories, Inc.
International
Inc.
AM-50 Series Amplifiers
AM-50-25
AM-50-70
Features
• Listed under UL® Standard 864, 9th Edition.
• Listed under UL Standard UL2572 for Mass
Notification.
• Complies with UL Standard 464 for 520 Hz Low
Frequency.
• Provides digital, switching amplifier technology.
• Produces 50 watts of digital power.
• Includes 2 speaker circuits, wired Style Y (Class B)
or Style Z (Class A).
• Up to 4 AM-50 Series amplifiers with the same out-
put voltage can be controlled by the INI-VGX voice
gateway.
SIGNALING
City of
FM MEA
Approved
APPROVED FDNY:
Chicago
Approved City of
Class 1 DENVER
S1869 3017416 COA #6077 7165-1703:0125 Class 2 Approved