EDSX6-135H Datasheet, PDF (2/8 Pages) Fuji Electric – DIFFERENTIAL PRESSURE (FLOW) TRANSMITTER Hydroseal® Diaphragm Version
FKC...5
Load limitations: see figure below
[Ω]
2000
1474Ω
1500 R= E-10.5
(Imax+0.9)x10-3
1000
500
250
577Ω
Operating
area
24V
45V
0
10 16.35
50 E[ V ]
10.5V
Power voltage (DC)
Note: For communication with HHC (Model: FXW), min. of 250 required.
Hazardous locations: (Under an application) See TABLE 2
Zero/span adjustment:
Zero and span are adjustable from the
HHC(1). Zero and span are also adjust-
able externally from the adjustment
screw.
Damping:
Adjustable from HHC or local configurator
unit with LCD display.
The time constant is adjustable between
0.06 to 32 seconds.
Zero elevation/suppression:
±100% to +100% of URL
Normal/reverse action:
Selectable from HHC(1)
Indication:
Analog indicator or 5-digit LCD meter, as
specified.
Burnout direction: Selectable from HHC(1)
If self-diagnostic detect transmitter fail-
ure, the analog signal will be driven to ei-
ther “Output Hold”, “Output Overscale”
or “Output Underscale” modes.
“Output Hold”:
Output signal is hold as the value just
before failure happens.
“Output Overscale”:
Adjustable within the range 20.0mA to
22.5mA from HHC(1)
“Output Underscale”:
Adjustable within the range 3.2mA to
4.0mA from HHC(1)
3.2
4
20
22.5 [mA]
Over scale
Burnout
Under scale
Normal operating range
Burnout
Probable under range
Probable over range
Loop-check output:
Transmitter can be configured to provide
constant signal 3.2mA through 22.5mA
by HHC(1).
Temperature limit:
Ambient: −40 to +85°C
(−20 to +80°C for LCD indicator)
(− 40 to +60°C for arrester option)
(−10 to +60°C for fluorinated oil filled
transmitters)
For explosionproof units (flameproof
or intrinsic safety), ambient tempera-
ture must be within the limits speci-
fied in each standard.
Process: −40 to +120°C for silicone fill
sensor
−20 to +80°C for fluorinated oil fill
sensor
Storage: −40 to +90°C
Humidity limit: 0 to 100% RH
Communication: With HHC(1) (Model FXW, consult Data
Sheet No. EDS8-47), following items can
be remotely displayed or configured.
Note: HHC’s version must be higher than 7.0
(or FXW
1− 4), for FCX–AIII.
Local configurator with LCD display (option):
Local configurator with 3 push button
and LCD display can support following
items.
Items
By communication By local configurator
with FXW (with 3 push button)
Display Set Display Set
Tag No.
v
v
v
v
Model No.
v
v
v
v
Serial No. & Software Version
v
—
v
—
Engineering unit
v
v
v
v
Range limit
v
—
v
—
Measuring range
v
v
v
v
Damping
v
v
v
v
Linear
v
v
v
v
Output mode
Square root
v
v
v
v
Burnout direction
v
v
v
v
Calibration
v
v
v
v
Output adjust
—
v
—
v
Data
v
—
v
—
Self diagnoses
v
—
v
—
Printer (In case of FXW with
printer option)
v
—
—
—
External switch lock
v
v
v
v
Transmitter display
v
v
v
v
Linearize
v
v
—
—
Rerange
v
v
v
v
Saturate current
v
v
v
v
Write protect
v
v
v
v
History
– Calibration history
v
v
v
v
– Ambient temperature history
v
—
v
—
Programmable output linearization function:
Output signal can be characterized with
“14 points linear approximation func-
tion” from HHC(1).
EMC Conformity: EN61326-1: 2006
Performance specifications for linear output
Reference conditions, silicone oil fill, 316SS isolating diaphragms, 4
to 20mA analog output in linear mode.
Accuracy rating: (including linearity, hysteresis, and re-
peatability)
Linear output : ±0.15%
Square root output : 50 to 100% 0.15%
20 to 50%
0.375%
10 to 20%
0.75%
Stability:
±0.15% of upper range limit (URL) for
10 years.
(Note) (1) HHC: Hand Held Communicator