EDSX5-98G Datasheet, PDF (1/8 Pages) Fuji Electric – PRESSURE TRANSMITTER (DIRECT MOUNT TYPE)
PRESSURE TRANSMITTER (DIRECT MOUNT TYPE)
DATA SHEET
FKP...5
The FCX– AIII pressure transmitter accurately measures
gauge pressure and transmits proportional 4 to 20mA
signal.
The transmitter utilizes the unique micromachined capaci-
tive silicon sensor with state-of-the-art microprocessor tech-
nology to provide exceptional performance and functionality.
FEATURES
1. High accuracy ±0.1%
0.1% accuracy is a standard feature. Fuji’s micro-capaci-
tance silicon sensor assures this accuracy for all elevated
or suppressed calibration ranges without additional adjust-
ment.
2. Minimum environmental influence
The “Advance Floating Cell” design which protects the
pressure sensor against changes in temperature, and
overpressure substantially reduces total measurement
error in actual field applications.
3. Fuji/HART® bilingual communications protocol
FCX– AIII series transmitter offers bilingual communica-
tions to speak both Fuji proprietary protocol and HART®.
Any HART® compatible devices can communicate with
FCX– AIII.
4. Application flexibility
Various options that render the FCX– AIII suitable for
almost any process applications include:
– Full range of hazardous area approvals
– Built-in RFI filter and lightning arrester
– 5-digit LCD meter with engineering unit
5. Burnout current flexibility (Under Scale: 3.2 to 4.0mA,
Over Scale: 20.0 to 22.5mA)
Burnout signal level is adjustable using Model FXW
Hand Held Communicator (HHC) to comply with NAMUR
NE43.
6. Dry calibration without reference pressure
Thanks to the best combination of unique construction
of mechanical parts (Sensor unit) and high performance
electronics circuit (Electronics unit), reliability of dry
calibration without reference pressure is at equal level
as wet calibration.
SPECIFICATIONS
Functional specifications
Service:
Liquid, gas, or vapour
Span, range and overrange limit:
Type
Span limit [kPa] {bar}
Min.
Max.
Range limit
[kPa] {bar}
Overrange
limit
[MPa] {bar}
FKP ˘ 01
FKP ˘ 02
FKP ˘ 03
FKP ˘ 04
8.125
{0.08125}
31.25
{0.3125}
187.5
{1.875}
625
{6.25}
130
{1.3}
500
{5}
3000
{30}
10000
{100}
−100 to +130
{−1 to +1.3}
−100 to +500
{−1 to +5}
−100 to +3000
{−1 to +30}
−100 to +10000
{−1 to + 100}
1
{10}
1.5
{15}
9
{90}
15
{150}
— Lower range limit (vacuum limit) is;
Silicone fill sensor: See Fig. 1
Fluorinated fill sensor: 66kPa abs (500mmHg abs) at
below 60°C
Output signal: 4 to 20mA DC with digital signal super-
imposed on the 4 to 20mA signal.
EDSX5-98g
Date Aug. 10, 2011