EDSX5-98G Datasheet, PDF (1/8 Pages) Fuji Electric – PRESSURE TRANSMITTER (DIRECT MOUNT TYPE) | |||
|
PRESSURE TRANSMITTER (DIRECT MOUNT TYPE)
DATA SHEET
FKP...5
The FCXâ AIII pressure transmitter accurately measures
gauge pressure and transmits proportional 4 to 20mA
signal.
The transmitter utilizes the unique micromachined capaci-
tive silicon sensor with state-of-the-art microprocessor tech-
nology to provide exceptional performance and functionality.
FEATURES
1. High accuracy ±0.1%
0.1% accuracy is a standard feature. Fujiâs micro-capaci-
tance silicon sensor assures this accuracy for all elevated
or suppressed calibration ranges without additional adjust-
ment.
2. Minimum environmental inï¬uence
The âAdvance Floating Cellâ design which protects the
pressure sensor against changes in temperature, and
overpressure substantially reduces total measurement
error in actual ï¬eld applications.
3. Fuji/HART® bilingual communications protocol
FCXâ AIII series transmitter offers bilingual communica-
tions to speak both Fuji proprietary protocol and HART®.
Any HART® compatible devices can communicate with
FCXâ AIII.
4. Application ï¬exibility
Various options that render the FCXâ AIII suitable for
almost any process applications include:
â Full range of hazardous area approvals
â Built-in RFI ï¬lter and lightning arrester
â 5-digit LCD meter with engineering unit
5. Burnout current ï¬exibility (Under Scale: 3.2 to 4.0mA,
Over Scale: 20.0 to 22.5mA)
Burnout signal level is adjustable using Model FXW
Hand Held Communicator (HHC) to comply with NAMUR
NE43.
6. Dry calibration without reference pressure
Thanks to the best combination of unique construction
of mechanical parts (Sensor unit) and high performance
electronics circuit (Electronics unit), reliability of dry
calibration without reference pressure is at equal level
as wet calibration.
SPECIFICATIONS
Functional speciï¬cations
Service:
Liquid, gas, or vapour
Span, range and overrange limit:
Type
Span limit [kPa] {bar}
Min.
Max.
Range limit
[kPa] {bar}
Overrange
limit
[MPa] {bar}
FKP Ë 01
FKP Ë 02
FKP Ë 03
FKP Ë 04
8.125
{0.08125}
31.25
{0.3125}
187.5
{1.875}
625
{6.25}
130
{1.3}
500
{5}
3000
{30}
10000
{100}
â100 to +130
{â1 to +1.3}
â100 to +500
{â1 to +5}
â100 to +3000
{â1 to +30}
â100 to +10000
{â1 to + 100}
1
{10}
1.5
{15}
9
{90}
15
{150}
â Lower range limit (vacuum limit) is;
Silicone ï¬ll sensor: See Fig. 1
Fluorinated ï¬ll sensor: 66kPa abs (500mmHg abs) at
below 60°C
Output signal: 4 to 20mA DC with digital signal super-
imposed on the 4 to 20mA signal.
EDSX5-98g
Date Aug. 10, 2011
|
▷ |